85
The CT Analyzer Test Cards
VA *
Cos
ϕ
Nominal burden of the CT, used to calculate the behavior of the CT at the
nominal burden.
Possible values: 0 to 300VA or soft keys
1.0VA
to
30VA
or
?
1
.
Depending on the burden and the selected test standard, the corresponding
cos
ϕ
is used (cos
ϕ
not editable by the user).
* This parameter is relevant for assessment. No automatic assessment is
available if the user did not enter data for this parameter prior to the test (see
page 82).
If the IEEE C57.13 standard is selected with the type "metering CT", the
CT Analyzer
offers some soft keys (e.g.
B-0.1
,
B-0.2
,
B-0.5
etc.) with
standard loads for the power. If these soft keys are used, the power is
calculated according to table 9 of IEEE C57.13. If the rated current is not 5A,
the resistance and inductance of the table is multiplied by the factor
If the IEEE C57.13 standard is selected with the type "protection CT" (class
C, K or T), the VA and Cos
ϕ
parameters are not accessible to the user. In
this case, the user has to enter the terminal voltage V
b
parameters and settings displayed for IEEE C57.13 protection CTs" on
page 98.
Burden
Cos
ϕ
"Burden" and "Cos
ϕ
" are used to define the operating burden connected to
the CT. These parameters are used to calculate the behavior of the CT at
the operating burden (connected burden) and the corresponding cos
ϕ
.
Possible values for "Burden": 0 to 300VA or soft keys
1.0VA
to
30VA
or
?
1
.
Possible values for "Cos
ϕ
": 0 to 1.
These parameters can also be changed after the test or in a loaded test
report in order to check the CT behavior at different burden values.
Special behavior depending on available test cards:
If the test contains a
Burden
card, a question mark is automatically entered
to the fields "Burden" and "cos
ϕ
" and entering the burden is not possible
until the test is finished. In this case, the value determined during the burden
test is automatically entered after burden measurement. If I
sn
is defined, the
burden is updated immediately after the burden test is finished. If I
sn
is not
defined (entry "?"), the burden is updated after the resistance test.
f
Rated frequency of the CT.
Possible values: Integer value between 16 and 400 Hz or soft keys
16.7Hz
,
50Hz
,
60Hz
or
400Hz
.
Default: Frequency defined in the default test settings.
Parameter
Description
α
5
I
rated
-------------
2
=
Summary of Contents for CT Analyzer
Page 1: ...CT Analyzer CT SB2 User Manual...
Page 3: ...CT Analyzer User Manual...
Page 4: ...CT Analyzer User Manual 2 Manual Version CTAnalyzerUM AE 3...
Page 39: ...37 Setup and Connection Figure 2 15 Measurement setup for delta compensation Ratio 1 L2 L3 L1...
Page 50: ...CT Analyzer User Manual 48...
Page 60: ...CT Analyzer User Manual 58...
Page 80: ...CT Analyzer User Manual 78...
Page 162: ...CT Analyzer User Manual 160...
Page 172: ...CT Analyzer User Manual 170...
Page 188: ...CT Analyzer User Manual 186...
Page 194: ...CT Analyzer User Manual 192...
Page 195: ...CT SB2 User Manual...
Page 196: ...CT SB2 User Manual 2 Manual Version CTSB2 AE 3...
Page 204: ...CT SB2 User Manual 10...
Page 206: ...CT SB2 User Manual 12...
Page 211: ...17 Hardware 1 x Cable bag Bag for cables and accessories Accessories Description...
Page 212: ...CT SB2 User Manual 18...
Page 226: ...CT SB2 User Manual 32...
Page 242: ...CT SB2 User Manual 48...
Page 248: ...CT SB2 User Manual 54...
Page 250: ...CT SB2 User Manual 56...
Page 252: ...CT SB2 User Manual 58...