21
Measurement Setup
3.3
Basic Measurement Setup for Multi-Ratio CT Testing
Figure 3-2
Basic measurement setup for multi-ratio CT testing (6 tap CT,
no burden measurement, no primary winding resistance
measurement)
X1
X2
X3
X4
X5
X6
*
*
Burden
Wiring for burden
measurement see
Figure 3-4
CT
*
For information how to connect the communication link between the
CT SB2
and the
CT Analyzer
, please refer to section 3.2 on page 20.
Warning:
Feeding test voltage to a tap of a multi-ratio CT can cause life-
threatening voltages on other taps with higher ratios. Always connect all
secondary taps to the
CT SB2
switch box in order to guarantee safety during
testing.
Summary of Contents for CT Analyzer
Page 1: ...CT Analyzer CT SB2 User Manual...
Page 3: ...CT Analyzer User Manual...
Page 4: ...CT Analyzer User Manual 2 Manual Version CTAnalyzerUM AE 3...
Page 39: ...37 Setup and Connection Figure 2 15 Measurement setup for delta compensation Ratio 1 L2 L3 L1...
Page 50: ...CT Analyzer User Manual 48...
Page 60: ...CT Analyzer User Manual 58...
Page 80: ...CT Analyzer User Manual 78...
Page 162: ...CT Analyzer User Manual 160...
Page 172: ...CT Analyzer User Manual 170...
Page 188: ...CT Analyzer User Manual 186...
Page 194: ...CT Analyzer User Manual 192...
Page 195: ...CT SB2 User Manual...
Page 196: ...CT SB2 User Manual 2 Manual Version CTSB2 AE 3...
Page 204: ...CT SB2 User Manual 10...
Page 206: ...CT SB2 User Manual 12...
Page 211: ...17 Hardware 1 x Cable bag Bag for cables and accessories Accessories Description...
Page 212: ...CT SB2 User Manual 18...
Page 226: ...CT SB2 User Manual 32...
Page 242: ...CT SB2 User Manual 48...
Page 248: ...CT SB2 User Manual 54...
Page 250: ...CT SB2 User Manual 56...
Page 252: ...CT SB2 User Manual 58...