145
Using the Quick Test Feature
8.5
Polarity Check
This measurement type is exclusively intended for polarity checks using
the
CPOL
polarity checker as described below. Do not use this mode for
any other measurements!
Note:
The Polarity Check measurement type requires the
CPOL
polarity
checker from OMICRON (order number VEHZ 0650).
Polarity Check is a predefined measurement type, intended especially for
checking a series of test points (e.g., the connecting terminals of the burden
wiring) for correct polarity. For this purpose, the
CT Analyzer
injects a signal with
a special waveform similar to a saw-tooth signal with a different steepness for
the rising and the falling slope. The
CPOL
polarity checker from OMICRON
checks the polarity of the injected signal and provides a clear indication as to
whether the polarity is OK or not.
Checking the polarity using the Polarity Check measurement type is much faster
than conventional methods and can easily be performed by a single person.
To select the Polarity Check measurement type, use the
cursor key to
move the cursor to the
Measurement Type
field in the
CT-Quick
card and then
press the
Polarity Check
soft key.
Figure 8-6
CT-Quick
card and
Results
card for the Polarity Check
measurement type
For the
Polarity Check
measurement type, the
CT-Quick
card holds the
following measurement quantities:
Parameter
Description
Output
The output signal type is fixed to "AC".
U/I
Operating mode of the internal signal generator: voltage or
current source. Fixed to "Current".
Amplitude
Current value of the polarity check signal. Adjustable by the
user.
Possible values: 0 to 7A. Default: 1.00A.
Press the
Main
soft key in
any test card
Main Menu:
- New Quick-Test
OK
soft key
CT-Quick
card:
Measurement Type:
Polarity Check
How to get there:
Summary of Contents for CT Analyzer
Page 1: ...CT Analyzer CT SB2 User Manual...
Page 3: ...CT Analyzer User Manual...
Page 4: ...CT Analyzer User Manual 2 Manual Version CTAnalyzerUM AE 3...
Page 39: ...37 Setup and Connection Figure 2 15 Measurement setup for delta compensation Ratio 1 L2 L3 L1...
Page 50: ...CT Analyzer User Manual 48...
Page 60: ...CT Analyzer User Manual 58...
Page 80: ...CT Analyzer User Manual 78...
Page 162: ...CT Analyzer User Manual 160...
Page 172: ...CT Analyzer User Manual 170...
Page 188: ...CT Analyzer User Manual 186...
Page 194: ...CT Analyzer User Manual 192...
Page 195: ...CT SB2 User Manual...
Page 196: ...CT SB2 User Manual 2 Manual Version CTSB2 AE 3...
Page 204: ...CT SB2 User Manual 10...
Page 206: ...CT SB2 User Manual 12...
Page 211: ...17 Hardware 1 x Cable bag Bag for cables and accessories Accessories Description...
Page 212: ...CT SB2 User Manual 18...
Page 226: ...CT SB2 User Manual 32...
Page 242: ...CT SB2 User Manual 48...
Page 248: ...CT SB2 User Manual 54...
Page 250: ...CT SB2 User Manual 56...
Page 252: ...CT SB2 User Manual 58...