CT Analyzer User Manual
174
210.xxx
Warning [210.xxx] Permanent data overflow.
Reason:
Internal data buffer overflow. The data could not be fetched fast enough from
the internal data buffer.
Solution:
Try to repeat the measurement. If this error occurs more frequently, you should
contact your next OMICRON service center.
211.xxx
Warning [211.xxx] AC mode measurement timeout.
Reason:
Measurement timeout due to frequent range switching or invalid data from the
measurement inputs.
Solution:
Check the wiring and repeat the measurement. Try to reduce noise for the
measurement.
220.xxx
Warning [220.xxx] Test aborted!
Reason:
The test sequence has been interrupted by the user.
Solution:
Repeat the test without interrupting it.
308.xxx
Note [308.xxx] I-sn value has to be specified in CT-Object Card prior to Residual
Magnetism test!
Reason:
For the remanence test the I
sn
value should be defined.
Solution:
Enter valid I
sn
value before starting the remanence test.
310.xxx
Note [310.xxx] License: <Guesser functionality> is missing! Values for: Ipn, Isn, P/M,
Class, FS/ALF should be provided.
Reason:
The license required for class guessing is not available.
Solution:
Specify the values for I
pn
, I
sn
, Class, P/M and FS/ALF before starting the test.
311.xxx
Warning [311.xxx] License: <Simulation after test> is missing!
Reason:
The license required for simulation is not available.
Solution:
Simulation of the results for changed test settings (e.g. different burden values)
after the test is not possible. Purchase a corresponding license.
312.xxx
Warning [312.xxx] License: <...> is missing!
Reason:
The license specified in the message is not available.
Solution:
The functionality included in the license is not available. Purchase a
corresponding license.
313.xxx
Warning [313.xxx] License: <All languages> is missing! Test can be performed only if
the Chinese user interface is set.
Reason:
The license required to use all languages is not available.
Solution:
Perform the test with the Chinese user interface or purchase a corresponding
license.
318.xxx
Warning [318.xxx] License: <Burden guesser> is missing! Values for VA, Burden, Cos
ϕ
should be provided.
Reason:
The license required for the burden guesser functionality is not available.
Solution:
Specify the values for nominal and operating burden (VA, Burden and cos
ϕ
) or
purchase a corresponding license.
319.xxx
Warning [319.xxx] License: <Quick test> is missing!
Reason:
The license required for the Quick Test functionality is not available.
Solution:
Purchase a corresponding license if you want to perform measurements using
Quick Test.
331.xxx
Note [331.xxx] Ipn is invalid! The value must be between the Ipn values of the
neighboring taps.
Reason:
An invalid I
pn
value has been entered to the
MR-Config.
card.
Solution:
Enter a valid I
pn
value.
Summary of Contents for CT Analyzer
Page 1: ...CT Analyzer CT SB2 User Manual...
Page 3: ...CT Analyzer User Manual...
Page 4: ...CT Analyzer User Manual 2 Manual Version CTAnalyzerUM AE 3...
Page 39: ...37 Setup and Connection Figure 2 15 Measurement setup for delta compensation Ratio 1 L2 L3 L1...
Page 50: ...CT Analyzer User Manual 48...
Page 60: ...CT Analyzer User Manual 58...
Page 80: ...CT Analyzer User Manual 78...
Page 162: ...CT Analyzer User Manual 160...
Page 172: ...CT Analyzer User Manual 170...
Page 188: ...CT Analyzer User Manual 186...
Page 194: ...CT Analyzer User Manual 192...
Page 195: ...CT SB2 User Manual...
Page 196: ...CT SB2 User Manual 2 Manual Version CTSB2 AE 3...
Page 204: ...CT SB2 User Manual 10...
Page 206: ...CT SB2 User Manual 12...
Page 211: ...17 Hardware 1 x Cable bag Bag for cables and accessories Accessories Description...
Page 212: ...CT SB2 User Manual 18...
Page 226: ...CT SB2 User Manual 32...
Page 242: ...CT SB2 User Manual 48...
Page 248: ...CT SB2 User Manual 54...
Page 250: ...CT SB2 User Manual 56...
Page 252: ...CT SB2 User Manual 58...