123
The CT Analyzer Test Cards
Note:
Values that caused a failed assessment are highlighted by black
background in the tables. Values without the prefix "!" have guaranteed
accuracy. The accuracy of values marked with a "!" in the tables is reduced by
factor 2.
Note:
For IEC 60044-1 metering CTs with I
sn
= 5A, it is possible to increase the
minimum
nominal burden
used for the assessment to 3.75VA in the device
settings (
Main Menu
, entry "Settings" ->
Setting Menu
, entry "Min. VA at M
cores Isn 5A"). In this case, the lowest nominal burden value displayed in the
ratio table and the phase table is 3.75VA instead of 1VA. Please note that this
only applies if the results are displayed with the nominal burden. It has no effect
if the results in the ratio table and the phase table are displayed with the
operating burden.
6.7.5
Ratio Table and Phase Table for IEEE C57.13
To display the ratio table or the phase table, press the
Ratio Table
or
Phase Table
soft key in the
Ratio
card.
If the selected standard is
IEEE C57.13
, these tables show the ratio error and
the phase displacement
• for different current values between 1% and 200% of the rated current.
• at the burden specified in the
CT-Object
card ("VA" or "Burden" parameter)
and all burden values defined in the IEEE C57.13 standard that are smaller
than the specified burden.
Use the
Results with Op. Burden
or
Results with Nom. Burden
soft key
to display the results related to the operating burden ("Burden" parameter in
the
CT-Object
card) or related to the nominal burden ("VA" parameter in the
CT-Object
card).
Note:
If the
Assess @ VA
option has been selected for the "Class"
parameter of an IEEE C57.13 metering CT in the
CT-Object
card, the tables
only show the ratio error and the phase displacement for the burden value
specified in the
CT-Object
card.
Note:
If a high accuracy license is available for IEEE C57.13, metering
burdens also include the electronic burdens.
The ratio table and the phase table contain all measurement points defined in
the IEEE C57.13 standard.
Use the
and
cursor keys to scroll through the table columns
(1% of rated current to 200% of rated current) and table lines (burden values).
Summary of Contents for CT Analyzer
Page 1: ...CT Analyzer CT SB2 User Manual...
Page 3: ...CT Analyzer User Manual...
Page 4: ...CT Analyzer User Manual 2 Manual Version CTAnalyzerUM AE 3...
Page 39: ...37 Setup and Connection Figure 2 15 Measurement setup for delta compensation Ratio 1 L2 L3 L1...
Page 50: ...CT Analyzer User Manual 48...
Page 60: ...CT Analyzer User Manual 58...
Page 80: ...CT Analyzer User Manual 78...
Page 162: ...CT Analyzer User Manual 160...
Page 172: ...CT Analyzer User Manual 170...
Page 188: ...CT Analyzer User Manual 186...
Page 194: ...CT Analyzer User Manual 192...
Page 195: ...CT SB2 User Manual...
Page 196: ...CT SB2 User Manual 2 Manual Version CTSB2 AE 3...
Page 204: ...CT SB2 User Manual 10...
Page 206: ...CT SB2 User Manual 12...
Page 211: ...17 Hardware 1 x Cable bag Bag for cables and accessories Accessories Description...
Page 212: ...CT SB2 User Manual 18...
Page 226: ...CT SB2 User Manual 32...
Page 242: ...CT SB2 User Manual 48...
Page 248: ...CT SB2 User Manual 54...
Page 250: ...CT SB2 User Manual 56...
Page 252: ...CT SB2 User Manual 58...