CT Analyzer User Manual
84
Class *
Accuracy class of the CT.
Possible values: Depending on the selected standard or
?
1
.
Default: As defined in the default test settings.
This parameter is only displayed, after the parameters "Standard" and "P/M"
have been defined or determined by the
CT Analyzer
. Depending on these
parameters, the parameters for the CT class can be selected using the soft
keys.
Note:
The class can be selected by soft keys or is determined by the
CT Analyzer
during the test. Automatic determination during the test only
works for IEC 61869-2 or IEC 60044-1 metering CTs and IEEE C57.13
metering CTs. If the question mark has been entered for the "P/M" parameter,
the "Class" cannot be defined by the user but is automatically determined by
the
CT Analyzer
instead.
* This parameter is relevant for assessment. No automatic assessment is
available if the user did not enter data for this parameter prior to the test (see
page 82).
For IEEE C57.13 metering CTs only:
An additional soft key
Assess @ VA
is available for metering CTs according
to IEEE C57.13. Use this option if the accuracy class of the CT only applies
to one specific burden.
CT assessment is normally performed for the maximum burden specified
("VA" or "Burden" parameter)
and
all lower burdens defined in the standard.
Example: If the burden specified is B-0.9, the assessment is performed for
the burdens B-0.9, B-0.5, B-0.2 and B-0.1 (and the electronic burdens E-0.2
and E-0.04).
Selecting the
Assess @ VA
option in addition to the class setting will cause
the
CT Analyzer
to consider
only
the burden value specified prior to testing
for the CT assessment. The ratio table and the phase table in the
Ratio
card
then only show the error for this specific burden (see section 6.7.5 on page
123).
When
Assess @ VA
is selected, the soft key changes to
Assess all VA
to
enable deactivation of this option.
Parameter
Description
Summary of Contents for CT Analyzer
Page 1: ...CT Analyzer CT SB2 User Manual...
Page 3: ...CT Analyzer User Manual...
Page 4: ...CT Analyzer User Manual 2 Manual Version CTAnalyzerUM AE 3...
Page 39: ...37 Setup and Connection Figure 2 15 Measurement setup for delta compensation Ratio 1 L2 L3 L1...
Page 50: ...CT Analyzer User Manual 48...
Page 60: ...CT Analyzer User Manual 58...
Page 80: ...CT Analyzer User Manual 78...
Page 162: ...CT Analyzer User Manual 160...
Page 172: ...CT Analyzer User Manual 170...
Page 188: ...CT Analyzer User Manual 186...
Page 194: ...CT Analyzer User Manual 192...
Page 195: ...CT SB2 User Manual...
Page 196: ...CT SB2 User Manual 2 Manual Version CTSB2 AE 3...
Page 204: ...CT SB2 User Manual 10...
Page 206: ...CT SB2 User Manual 12...
Page 211: ...17 Hardware 1 x Cable bag Bag for cables and accessories Accessories Description...
Page 212: ...CT SB2 User Manual 18...
Page 226: ...CT SB2 User Manual 32...
Page 242: ...CT SB2 User Manual 48...
Page 248: ...CT SB2 User Manual 54...
Page 250: ...CT SB2 User Manual 56...
Page 252: ...CT SB2 User Manual 58...