EN
10
– English
Possible causes of malfunctions are listed below, which may occur during the
installation phase, or in the case of faults, possible remedies:
• The radio transmitter does not control the barrier and the transmit-
ter led does not illuminate:
Check that the transmitter batteries are not dis-
charged and replace if necessary .
• The radio transmitter does not control the barrier but the transmitter led illumi-
nates: check that the transmitter is correctly memorised on the radio receiver .
Ensure correct emission of the radio signal of the transmitter with the following
empirical test: Press a key and place the led against the aerial of a standard
radio switched on and tuned to FM at the frequency of 108 .5Mhz or as close
to this value as possible; a slight noise with a scratching pulse noise should be
heard .
• No manoeuvre is performed when a command is sent, and the OK
led does not flash:
check that the barrier is powered via the mains at 230 V.
Also check that the fuses F1 and F2 are not blown; in this case try to locate the
cause of the fault and then replace with a version with the same specifications;
see
fig. 42
.
• No manoeuvre is performed when a command is sent, and the flash-
ing light remains off:
check that the command is effectively received; if the
sent command reaches the SS input, the OK led emits a double flash to indi-
cate that the command is received .
• The manoeuvre does not start and the courtesy light flashes a few
ti mes:
count the number of flashes and check with reference to the data in
Table 9
in Chapter 8 .
• The manoeuvre is performed, but shortly afterwards the pole blocks and
performs a brief inversion: the selected force value may be too low to enable
movement of the pole . Check correct balancing of the pole; if necessary set a
higher force value .
WHAT TO DO IF…
(troubleshooting guide)
7
8.1 - Total deletion of control unit memory
It is possible to delete all memorised data on the control unit and reset it to the
original factory settings:
01.
Press and hold down “
s
“ and “
t
“ keys at the same time;
02.
Release the keys when all Led illuminate (after approx.3 seconds);
03.
When leds
L1
and
L2
start flashing, this means that the procedure is termi-
nated .
Important
– This procedure does not delete the parameter regarding the
direction of motor rotation and the number of manoeuvres performed .
8.2 - Other functions
• “Always open” function
This function is a special feature of the control unit; it is associated with the
“Step Step” input and enables an “always open” command when the Step
Step command remains active for more than 3 seconds . This function is valid
for any setting of the Step Step input (see “SS Function” in
Table 7
) .
For example, it can be used to connect a clock for programming permanent
opening of the barrier during a specific time band.
• “Move anyway” function
If one or more safety devices malfunctions or is out of service, this function
enables control of the barrier in “hold-to-run” mode (for details, see chapter
“operation manual”) .
• “Maintenance notification” function
This function enables notification of when an automation maintenance check is
necessary. The “Maintenance notification” parameter can be set with a value on
8 different levels (see
Table 7
) .
The levels refer to the number of manoeuvres performed . The maintenance
notification is signalled via the Flash flashing light or by the maintenance indica-
tor according to the type of setting. The signals emitted by the Flash flashing
light and the maintenance indicator are shown in
Table 9
.
• Check of number of manoeuvres performed
The function “Maintenance notification” enables the user to check the number
of manoeuvres performed as a percentage of the maximum set limit. Proceed
as shown in
Table 10
.
• Manoeuvre counter reset
The manoeuvres can be reset at the end of the automation maintenance phase .
To proceed, see
Table 11
.
FURTHER DETAILS
8
TABLE 9
Number of manoeuvres
Flash flashing light
Maintenance indicator
Below 80% of the limit
Normal (0.5 sec. lit - 0.5 sec. off)
Light on for 2 seconds at the start of the
opening manoeuvre .
Between 81% and 100% of the limit
Light on for 2 seconds at the start of the manoeuvre.
Flashing for entire duration of manoeuvre then
continuing as normal
Over 100% of the limit
At the start and end of the manoeuvre, remains lit
Always flashes
for 2 sec ., then continues as normal .
TABLE 8 - Programming procedure (second level functions)
01.
Press and hold down the “
Set
” key for approx. 3 seconds;
02.
Release the key when LED
L1
starts flashing;
03.
Press keys “
s
” or “
t
” to move from the flashing led to the led associated with the function to be modified;
04.
Press and hold the “
Set
” key through to completion of point 06;
05.
Wait approx. 3 seconds, until the LED representing the current level of the parameter to be modified illuminates;
06.
Press keys
s
or
t
to move the LED representing the value of the parameter;
07.
Release the “
Set
” key;
08.
Wait 10 seconds (maximum time) to exit the programming mode.
Note
– During this procedure, points 03 to 07 need to be repeated when programming other parameters during the phase itself .
10 s
3 s
SET
SET
SET
L1
SET
/
/
Summary of Contents for S4BAR
Page 2: ......
Page 20: ......
Page 40: ......
Page 60: ......
Page 80: ......
Page 100: ......
Page 120: ......
Page 140: ......
Page 143: ...I I 1 A B C B 330 mm 2 179 5 mm 1146 mm 826 mm 4000 mm 3 b a d e f g h c...
Page 144: ...II II 5 A B C 1 2 4...
Page 145: ...III III 9 10 90 6 A C B 7 8 B A...
Page 146: ...IV IV 14 A B 15 A B 11 A B 12 13 A B...
Page 147: ...V V 16 A B 17 18...
Page 148: ...VI VI 20 180 21 C C A B 1cm 1cm 19 A C B...
Page 149: ...VII VII 22 23 26 L N 24 1 2 25...
Page 151: ...IX 30 A A B STOP 31 A B...
Page 152: ...X 32 A B C D STOP 33 A B 34...
Page 154: ...XII 300 200 700 500 39 300 200 700 500 150 40 41...
Page 155: ...a c d e b F2 F1 42 43 XIII...
Page 156: ...XIV 44 O pe n L1 L2 L3 L4 L5 L6 L7 L8 St op Se t Cl os e Fuse 1AT 45 f g...
Page 157: ......
Page 158: ......
Page 159: ......