Service menus
40
SMO 10
Menu 9.1.0 Heat pump settings
Settings concerning FIGHTER 2010 / 2005 are made
in the sub-menus to this.
H e a t p u m p s e t t i n g s
9 . 1 . 0
Menu 9.1.1 Compressor starts at
Degree minute setting for start of FIGHTER 2010 /
2005. The value is adjustable between -120 and 0.
- 6 0
C o m p r e s s o r s t a r t s a t
9 . 1 . 1
Menu 9.1.2 Number of F2010
Number of connected FIGHTER 2010s / 2005s. The
value is adjustable between 0 and 9.
1
N u m b e r o f F 2 0 1 0
9 . 1 . 2
Menu 9.1.3 Start defrost*
The required start temperature on the evaporator sen-
sor for defrosting of FIGHTER 2010 / 2005 is set here.
The value is adjustable between -10 and +2 °C.
- 4 ° C
S t a r t d e f r o s t ( 0 6 )
9 . 1 . 3
Menu 9.1.5 Max defrost time*
The longest time for defrosting of FIGHTER 2010 /
2005 is selected here. The value is adjustable
between 5 and 12 minutes.
7 m i n
M a x d e f r o s t t i m e ( 0 9 )
9 . 1 . 5
Menu 9.1.7 Powerstepup*
Outdoor air temperature, to change the power step in
FIGHTER 2010. The value is adjustable between 0
and 40 °C.
1 0 ° C
P o w e r s t e p u p ( 1 4 )
9 . 1 . 7
Menu 9.1.6 Time betw. defr*
Minimum running time, heat production before new
defrosting is permitted in FIGHTER 2010 / 2005. The
value is adjustable between 10 and 90 minutes.
5 0 m i n
T i m e b e t w . d e f r ( 1 0 )
9 . 1 . 6
Menu 9.1.8 Drip tray heater*
Outdoor air temperature, for start of the drip tray
heater in FIGHTER 2010 / 2005. The value is
adjustable between -2 and 2 °C.
2 ° C
D r i p t r a y h e a t e r ( 1 6 )
9 . 1 . 8
Menu 9.1.4 Stop defrost(07)*
The required stop temperature on the evaporator sen-
sor for defrosting of FIGHTER 2010 / 2005 is set here.
The value is adjustable between 10 and 40 °C.
2 0 ° C
S t o p d e f r o s t ( 0 7 )
9 . 1 . 4
S
S
S
S
S
S
S
S
S
*
The numbers in brackets denote the corresponding
channel number in FIGHTER 2010 / 2005.
Heat pump settings
Summary of Contents for SMO 10
Page 1: ...R MOS GB 0521 1 511262 SMO 10 INSTALLATION AND MAINTENANCE INSTRUCTION SMO 10...
Page 2: ......
Page 50: ...Electrical circuit diagram 48 SMO 10 Sheet 1 4...
Page 54: ...Dimensions 52 SMO 10 405 406 151 5 328 276 Dimensions and setting out coordinates...
Page 58: ...SMO 10 56...
Page 59: ......