Control
32
SMO 10
Flow temperature
Menu 2.4 Max flow temp.
The set maximum level for the supply temperature to
the heating system is shown here. The value is
adjustable between 10 and 80 °C.
The calculated flow temperature never exceeds the
set level irrespective of the outdoor temperature,
curve slope or offset heating curve.
Menu 2.5 External adjustment
Connecting an external contact, see Electrical con-
nections - External contacts, for example, a room ther-
mostat or a timer allows you to temporarily or periodi-
cally raise or lower the flow temperature and with that
the room temperature. When the external contact is
made the calculated flow temperature is changed by
the number of degrees shown here. The value is
adjustable between -25 and +25 °C.
Menu 2.6.0 Own Curve Definition
You own curve definition is chosen here. This is an
individual linear curve with one break point. You select
a break point and the associated temperatures.
NOTE! The Curve slope in menu 2.1 must be set to 0
to activate this function.
Menu 2.6.1 Supply temp.at +20ºC
The flow temperature at an outside temperature of -20
is chosen here. The value is adjustable between 0 and
80 °C.
Menu 2.6.2 Supply temp.at-20ºC
The flow temperature at an outside temperature of -20
is chosen here. The value is adjustable between 0 and
80 °C.
Menu 2.6.3 Set temperature
Here you select at what outside temperature the break
point shall occur. The value is adjustable between -15
and +15 °C.
Menu 2.1 Curve coefficient
The selected curve slope (heating curve) is shown
here. The Own curve function is activated at value 0,
see menu 2.6.0. The value can be set between curve
0 and 20.
Menu 2.2 Offset heating curve
The selected heating curve offset is shown here. The
value is adjustable between -10 and +10. NOTE! The
value is changed using the Offset heating curve knob.
Menu 2.3 Min flow temp.
The set minimum level for the supply temperature to
the heating system is shown here. The value is
adjustable between 10 and 65 °C.
The calculated flow temperature never drops below
the set level irrespective of the outdoor temperature,
curve slope or offset heating curve.
5 5 ° C
M a x f l o w t e m p .
2 . 4
0 ° C
E x t e r n a l a d j u s t m e n t
2 . 5
1 5 ° C
S u p p l y T e m p . a t + 2 0 º C
2 . 6 . 1
3 5 ° C
S u p p l y T e m p . a t - 2 0 º C
2 . 6 . 2
0 ° C
S e t t e m p e r a t u r e
2 . 6 . 3
O w n C u r v e D e f i n i t i o n
2 . 6 . 0
9
C u r v e c o e f f i c i e n t
2 . 1
- 2
O f f s e t h e a t i n g c u r v e
2 . 2
1 5 ° C
M i n f l o w t e m p .
2 . 3
U
U
N
N
U
U
U
U
U
Summary of Contents for SMO 10
Page 1: ...R MOS GB 0521 1 511262 SMO 10 INSTALLATION AND MAINTENANCE INSTRUCTION SMO 10...
Page 2: ......
Page 50: ...Electrical circuit diagram 48 SMO 10 Sheet 1 4...
Page 54: ...Dimensions 52 SMO 10 405 406 151 5 328 276 Dimensions and setting out coordinates...
Page 58: ...SMO 10 56...
Page 59: ......