R100 component and environmental parameters
R100 component and environmental parameters
Installation
considerations
When planning your storage system installation, you must consider the
following:
◆
Physical characteristics, such as height and weight
◆
Environmental requirements, such as temperature and humidity
◆
Space requirements that you must have around the chassis
◆
Electrical requirements for the chassis
R100 system
environmental
conditions
The following table lists the environmental conditions that your site must meet to
properly run or store your chassis and disk shelves.
Freestanding
equipment rack
requirements
The freestanding equipment rack must meet the following requirements:
◆
A width of 19 inches (48.26 cm)
◆
Front installation rails compliant with EIA standard EIA-310-D
◆
Adequate space for air circulation directly above the chassis ventilation
holes
If you install a device above the chassis, leave at least 0.5 inches (1.3 cm) of
space directly above the ventilation holes. You can install equipment directly
on the unvented area as long as it does not extend over and block the
ventilation holes on the chassis.
Environmental condition
Operating condition
Storage condition
Temperature range
50
°
F to 104
°
F
(10
°
C to 40
°
C)
-4
°
F to 149
°
F
(-20
°
C to 65
°
C)
Relative humidity
(noncondensing)
10% to 90%
10% to 90% in
original shipping
container; otherwise,
50%.