6.
Remove reducing agent lines (blue) from RA
tank.
Installing reducing agent lines
1.
Ensure that all mating connectors are clean and free of deposits (e.g. urea crystals).
2.
Install new reducing agent lines in reverse order.
3.
Open supply and return line from pre-feed module to RA tank before starting engine.
MS15065/01E 2019-01
| Exhaust Gas Aftertreatment | 257
TIM-ID: 0000078955 - 003