1113 – AL Act Intake Temperature Warning
Cause
Corrective action
Internal electronics of the
servomotor of
thermomanagement flap 1
(M58.1) signal excessively high
temperature.
u
Contact Service.
1114 – AL Act Intake Air Targetposition
Cause
Corrective action
The servomotor of
thermomanagement flap 1
(M58.1) was unable to reach its
target position. The difference
between target position and
actual position exceeds limit value
1.
u
Contact Service.
1115 – AL Difference P0 P1 Intake Air L1
Cause
Corrective action
The differential pressure at sensor
B90 and the ambient air pressure
sensor integrated in the ECU have
violated limit value 1. The intake
air differential pressure is too
high.
1. Check air filter (plant side) for contamination.
2. Contact Service.
1116 – AL Difference P0 P1 Intake Air L2
Cause
Corrective action
The differential pressure at sensor
B90 and the ambient air pressure
sensor integrated in the ECU have
violated limit value 2. The intake
air differential pressure is too
high.
1. Check air filter (plant side) for contamination.
2. Contact Service.
1125 – AL Act Intake Air Calibr Drive Err
Cause
Corrective action
The ECU has detected a
calibration routine error of the
thermomanagement flap 1
(M58.1). Cause: The learned
rotation range (angle) during the
calibration run was not plausible.
The learned angle is not between
a minimum and maximum
admissible limit.
u
Contact Service.
MS15065/01E 2019-01
| Troubleshooting | 155
TIM-ID: 0000078552 - 003