92 – SS Starter Speed Not Reached
Cause
Corrective action
Engine speed has not reached the
specified speed threshold within
the specified time.
1. Check pressure supply (plant) of starter.
2. Check for additional messages.
3. Contact Service.
93 – SS T-Preheat
Cause
Corrective action
Engine coolant temperature has
not reached the specified limit
value 2. Preheating is not
functioning. Start interlock.
u
Contact Service.
94 – LO T-Preheat
Cause
Corrective action
Engine coolant temperature has
not reached the specified limit
value 1. Preheating is not
functioning.
u
Contact Service.
95 – AL Prelubrication Fault
Cause
Corrective action
The oil pressure at sensor B5.1
has violated the specified value.
The specified oil pressure was not
reached. The start procedure was
terminated.
1. Check engine cabling (→ Page 321).
2. Contact Service.
118 – LO ECU Power Supply Voltage
Cause
Corrective action
The supply voltage of the ECU has
violated limit value 1.
1. Check state of charge of batteries (plant side).
2. Check plug connections to Engine Control Unit (→ Page 323).
3. Check battery charging-generator.
4. Contact Service.
119 – LOLO ECU Power Supply Voltage
Cause
Corrective action
The supply voltage of the ECU has
violated limit value 2.
1. Check state of charge of batteries (plant side).
2. Check plug connections to Engine Control Unit (→ Page 323).
3. Check battery charging-generator.
4. Contact Service.
132 | Troubleshooting | MS15065/01E 2019-01