7. APPLICATION INSTRUCTIONS
7
−
102
MELSEC-A
CAUTION
Provide interlock using the special registers mentioned below so that the RTOP instruction may
be executed when the data link with remote I/O stations is normal and parameter communication
is not being performed.
Remote I/O station normal/error judgment: D9228 to D9231
Parameter communication execution/non-execution judgment: D9224 to D9227
For details, refer to the type MELSECNET, MELSECNET/B Data Link System Reference Manual
(IB(NA)-66350).
•
Coding
0 LD
X003
1 PLS
M1
4 LD
M1
5 SET
M0
6 LD
M0
7 MPS
8 ANI
Y14F
9 ANI
X15F
10
ANI
Y14E
11
ANI
X15E
12
RTOP
H0140
K10
W052
K10
23
MPP
24
AND
X15F
25
RST
M0
26
RST
Y14F
27
END
Turned OFF by the
sequence program.
Turned OFF by the
sequence program.
Executed only once.
Turned ON by
the special
function module.
For 2 link
scans
Executed only once.
Turned ON by
the special
function module.
RTOP
X11E
Y10E
M0
M1
X3
ON
ON
ON
OFF
OFF
OFF