7. APPLICATION INSTRUCTIONS
7
−
6
MELSEC-A
(3) Program which performs logical product of the data of X10 to 1B and the data of
D33, and sends the result to the Y30 to 3B when XA turns on.
DAND
(1) Program which performs logical product of the 24-bit data of X30 to 47 and the
data of D99 and 100, then transfers the result to the M80 to 103 when X8 turns
on.
X00A
0
P
K3
K3
WAND X010 D33 Y030
•
Coding
0 LD
X00A
1 WANDP K3X010 D33
K3Y030
8 END
Regarded as 0.
Do not change.
X008
0
P
K6
DAND X030
D99
P
K6
DMOV D99
M80
Logical product of the data of X30 to47 and the
data of D99 and 100 is performed and the result
is stored into D99 and 100.
Data of D99 and 100 is transferred to the M80 to
103.
•
Coding
0 LD
X008
1 DANDP K6X030 D99
10
DMOVP D99
K6M80
17
END
Regarded as 0.
Set to 0.