5. SEQUENCE INSTRUCTIONS
5
−
23
MELSEC-A
5.3.3 Edge-triggered differential output
(PLS, PLF)
Available Device
Bit device
Word (16-bit) device
Constant
Pointer
Level
Ca
rr
y
fla
g
Err
o
r
fla
g
X Y M L S B F T C D W R A0
A1
Z V K H P I N
D
igit specification
In
d
e
x
M9012 (M9010, M9011)
(D)
O
O
O
O
O
O
*1: Index qualification can be used with AnA, A2AS, AnU, QCPU-A (A Mode) and A2USH board only.
Function PLS
(1) When the PLS command changes from Off to On, the specified device goes On
for 1 scan and when the PLS command is in a state other than Off
→
On (Off
→
Off, On
→
On, On
→
Off), the device goes Off.
If there is one PLS instruction from the specified device (D) within 1 scan, the
specified device goes On for 1 scan.
See Section 3.9 concerning operation in the case that the PLS instruction from
the same device is executed multiple times in 1 scan.
PLS command
X005
PLS M0
PLS
PLS
PLS command
M0 OFF
X5 OFF
ON
ON
1 scan
Applicable
CPU
All CPUs
PLF command
(D)
(D)
(D)
Device number to be con-
verted into pulse
Setting data
1 scan
*1