7. APPLICATION INSTRUCTIONS
7
−
67
MELSEC-A
DFRO
Program which reads the data of two words from the address 10 of buffer memory of
A68AD, loaded in I/O numbers 040 to 05F to D0 and 1.
POINT
If a FROM instruction is executed for a special function module frequently in a
short scan time, the objective special function module may fail to process
correctly.
To execute a FROM instruction for a special function module, set the execution
intervals meeting the processing and conversion time of that module using the
timer and the constant scan function of it.
X000
0
H
K
K
DFRO 0004 10
D0 1
•
Coding
0 LD
X000
1 DFRO H0004 K10
D0
K1
10
END