6. BASIC INSTRUCTIONS
6
−
4
MELSEC-A
6.1.1 16-bit data comparison
(=, <>, >, <=, <, >=)
Available Device
Bit device
Word (16-bit) device
Constant
Pointer
Level
Ca
rr
y
fla
g
Err
o
r
fla
g
X Y M L S B F T C D W R A0
A1
Z V K H P I N
D
igit specification
In
d
e
x
M9012 (M9010, M9011)
(S1)
O O O O O O O O O O O O O O O O O O
(S2)
O O O O O O O O O O O O O O O O O O
K1
to
K4
O
O
Functions
(1) Handled as a NO contact and used for the comparison of 16bits.
(2) The comparison operation result is as shown below:
Instruction
Symbol in
Condition
Comparison
Operation
Result
Instruction
Symbol in
Condition
Comparison
Operation
Result
=
(S1) = (S2)
=
(S1)
≠
(S2)
<> (S1)
≠
(S2)
<>
(S1) = (S2)
>
(S1) > (S2)
>
(S1)
≤
(S2)
<= (S1)
≤
(S2)
<=
(S1) > (S2)
<
(S1) < (S2)
<
(S1)
≥
(S2)
>= (S1)
≥
(S2)
Continuity
status
>=
(S1) < (S2)
Non-Continuity
status
Execution
The execution conditions of LD , AND , and OR are as indicated below.
Conditions
Instruction Execution
Condition
LD
Executed per scan.
AND
Executed only when the preceding contact instruction is on.
OR
Executed per scan.
Applicable
CPU
All CPUs
(S1)
(S2)
Compared data or head
number of device which
stores compared data
Setting data
=, <>,>
<=, <, >=
Indicates the instruction symbol.
LD
AND
OR
(S1) (S2)
(S1) (S2)
(S1) (S2)
Summary of Contents for MELSEC-A series