4
FUNCTIONS
4.5 Self-Diagnostic Function
4
- 24
1
O
V
ER
VI
E
W
2
SY
STEM
CONFIGURA
TION
3
SP
ECIFICA
T
IONS
4
FUNCTIONS
5
A
C
C
E
SS V
IA
N
E
TW
OR
K
MODUL
ES
6
P
R
EP
AR
A
T
OR
Y
PROCE
DUR
ES
A
ND
S
E
TTING
7
I/O NUM
BER
ASS
IGN
M
EN
T
8
M
E
M
O
RIE
S
A
ND
FI
L
E
S
: Detectable
: Not detectable
* 6 The 7-segment LED flashes, indicating "01" or "02".
If this error has occurred, the C Controller module will not start.
* 7 The 7-segment LED flashes, indicating "00."
If this error has occurred, the C Controller module will not start.
* 8 Output is stopped only when a stop error occurs.
For a continuation error, output is not stopped.
Remark
For the C Controller setting utility, refer to the following.
C Controller Module User's Manual (Utility Operation, Programming)
Table 4.6 Self-diagnostic function list (continued)
Item
Description
C Controller
module
status
LED status
Diagnostic timing
Error handling
RUN
ERR.
1)
2)
3)
SRAM error detection
An error of the battery-backed-up
RAM (SRAM) is detected.
(The standard RAM ("/RAM") is
included.)
(The Q12DCCPU-V only)
Stop
Off
Flash
Any time
At power-on
*6
,
at reset
*6
Built-in ROM error
detection
*7
An error of the built-in ROM ("/
SYSTEMROM") is detected.
(The Q12DCCPU-V only)
Stop
Off
Flash
At power-on,
at reset
Other error detections
Stop/continue errors other than the
above are detected.
Continue
On
On
At power-on,
at reset,
periodic check
*8
Summary of Contents for Q06CCPU-V
Page 2: ......
Page 612: ...APPX 48 Appendix 11 Functions Added by Version Upgrade APPENDICES Memo ...