4.5 Self-Diagnostic Function
4
FUNCTIONS
: Detectable
: Not detectable
* 1 "Not checked" can be set in "Error check" in <<System settings>> of C Controller setting utility.
* 2 How many times a momentary stop was detected can be confirmed by the QBF_ReadStatusEx
function.
While the C Controller module is detecting "Main CPU error", "Momentary stop detection"
(including detection count update) and "Power OFF detection" are not performed.
* 3 The CPU operation status for error detection can be changed to "Continue" in "Operation mode at
the time of error" in <<System settings>> of C Controller setting utility.
* 4 The CPU operation status for error detection can be changed to "Continue" in "H/W error time CPU
operation mode" in <<I/O assignment settings>> of C Controller setting utility.
* 5 Whether to stop the multiple CPU system or not when an error occurs in CPU No.2, No.3, or No.4
can be set in "Operation mode" in <<Multiple CPU settings>> of C Controller setting utility.
(To the next page)
Table 4.6 Self-diagnostic function list
Item
Description
C Controller
module
status
LED status
Diagnostic timing
Error handling
RUN
ERR.
1)
2)
3)
System watchdog timer
error detection
A system watchdog timer error is
detected.
Stop
Off
Flash Any time
User watchdog timer
error detection
A user watchdog timer error is
detected.
Stop
Off
Flash Any time
Battery error detection
*1
A battery error of the C Controller
module is detected.
Continue
On
On
Periodic check
Momentary stop
detection
*2
A momentary stop is detected.
Continue
On
Off
Any time
Module verify error
detection
*1
The mounting condition of an I/O
module is diagnosed.
Stop/
Continue
*3
Off/On
Flash/
On
Periodic check
Blown fuse detection
*1
The condition of the fuse of an output
module is diagnosed.
Stop/
Continue
*3
Off/On
Flash/
On
Periodic check
Control bus error
detection
The condition of the bus on the base
unit is diagnosed.
Stop
Off
Flash
At power-on, at reset,
periodic check, or at
module access
Intelligent function
module error detection
An error in an intelligent function
module is detected.
Stop/
Continue
*4
Off/On
Flash/
On
At power-on, at reset,
periodic check,
at module access, or
when interrupt occurs
Intelligent function
module assignment
error detection
The I/O assignment status of an
intelligent function module is
diagnosed.
Stop
Off
Flash
At power-on or at
reset
Parameter error
detection
Parameters in the system setting,
multiple CPU setting, etc. are
diagnosed.
Stop
Off
Flash
At power-on or at
reset
Intelligent function
module parameter error
detection
Parameters for intelligent function
modules are diagnosed.
Stop
Off
Flash
At power-on or at
reset
Link parameter error
detection
Parameters for link modules (CC-Link
modules, MELSECNET/H modules,
CC-Link IE controller network
modules) are diagnosed.
Stop
Off
Flash
At power-on or at
reset
Multiple CPU error
detection
In a multiple CPU system
configuration, an error of another
CPU or inconsistency in the multiple
CPU system is detected.
Stop/
Continue
*5
Off/On
Flash/
On
Any time
At power-on or at
reset
Main CPU error
detection
*2
Failure of the power supply module or
C Controller module is detected.
Stop
Off
Flash
Any time
At power-on or at
reset
Power OFF detection
*2
AC/DC power failure is detected.
Continue
On
Off
Any time