![Mitsubishi Electric Q06CCPU-V User Manual Download Page 466](http://html.mh-extra.com/html/mitsubishi-electric/q06ccpu-v/q06ccpu-v_user-manual_1811831466.webp)
15
- 12
15.2 Setting Parameters Added for Multiple CPU Systems
15.2.3 When creating a new system
15
STARTING A MULTIPLE CPU SYSTEM
(From the previous page)
"Operation mode" in the <<Multiple CPU settings>> tab
(optional)
"I/O sharing when using Multiple CPUs" in the <<Multiple CPU
settings>> tab (optional)
"Communication area setting (refresh setting)" in the <<Multiple CPU
settings>> tab (optional)
(To the next page)
"Communication area setting (refresh setting)" in the <<Multiple CPU
settings>> tab (optional)
Select whether to stop or continue the operations of all CPUs in
the event of a stop error.
Default: All CPUs stop by a stop error in any of CPU
No. 2, 3 and 4 (Checked)
For example, when "All CPUs stopped due to an error in
CPU2" is unchecked, CPUs other than CPU No.2 will continue
their operations even if a stop error occurs in CPU No.2.
The operating mode of CPU No.1 cannot be changed.
Set whether to read input/output status data of non-controlled
modules or not.
Default: Not read. (Not checked)
"Online module change" in the <<Multiple CPU settings>> tab
(optional)
Determine whether to enable the online module change setting.
"Default: Online module change is disabled.
(Not checked)"
Do not check the check box when setting "I/O sharing when
using Multiple CPUs".
Check the check box when performing online module change.
The "Change screens" enables four different kinds of settings
(Setting 1 to Setting 4).
Set the points of data to be sent and received by auto refresh
between CPUs.
Summary of Contents for Q06CCPU-V
Page 2: ......
Page 612: ...APPX 48 Appendix 11 Functions Added by Version Upgrade APPENDICES Memo ...
Page 617: ......