11
MULTIPLE CPU SYSTEM CONFIGURATION
11.1 System Configuration
11.1.4 System configuration overview (when CPU No.1 is a C Controller module)
11
- 10
9
DE
V
ICE DE
S
CRIPT
IO
N
10
MU
LT
IPL
E
CP
U SY
S
T
EM
O
V
ER
VI
E
W
11
MUL
T
IP
L
E
CP
U
S
Y
S
TE
M
CONFIGURA
TION
12
CONCE
PT
OF MU
LT
IPL
E
CP
U SY
S
T
EM
13
COMMUN
ICA
TIO
N
S
BE
TWE
E
N
CP
U
MODUL
ES
14
P
A
RAM
E
TE
RS
A
DDE
D
F
O
R MU
LT
IP
LE
C
P
U
S
YSTE
M
S
15
ST
A
R
TIN
G A
M
U
LT
IPLE
CP
U
SYS
TEM
16
TR
O
U
B
L
E
S
HOOTING
Precautions
• The total extension cable length must be 13.2m (43.31 feet) or less.
• Do not install the extension cables together with the main circuit lines (high
voltage and large current).
• Set a unique number for each extension base.
• If some Q5 B and Q6 B extension base units are used on the same
system, they can be connected in any order.
However, confirm the applicability of each unit referring to the QCPU User's
Manual (Hardware Design, Maintenance and Inspection).
• The QA1S6 B and Q6 RB cannot be used as an extension base unit.
• Connect the extension cable from OUT of the extension cable connector of
the base unit to IN of the next extension base unit.
• Mounting 66 or more modules (including CPU modules) causes an intelligent
function module assignment error (error code: 2124, SP.UNIT LAY ERR.)
• "Number of CPUs" is the number of CPU modules set for "Number of CPUs"
in the <<Multiple CPU settings>> tab of C Controller setting utility.
• For details of the Motion CPU, refer to the manual for the Motion CPU.
• When the Q12DCCPU-V is CPU No.1, only the Q172DCPU and Q173DCPU
can be installed.
When the Q06CCPU-V(-B) is CPU No.1, no Motion CPU can be installed.
• Programmable controller CPUs cannot be installed.
Table 11.3 Restrictions on the system configuration
CPU number
CPU module 1: CPU No.1, CPU module2: CPU No.2, CPU module 3: CPU No.3, CPU module 4: CPU No.4
Maximum number of
extension base units
7 units
Maximum number of I/O
modules
65 minus (Number of CPUs)
Main base unit model
Q35DB, Q38DB, Q312DB
Extension base unit model
No power supply module required
Q52B, Q55B
Q series power supply module required
Q63B, Q65B, Q68B, Q612B
Extension cable model
QC05B, QC06B, QC12B, QC30B, QC50B, QC100B
Q series power supply
module model
Q61P-A1, Q61P-A2, Q61P, Q61P-D, Q62P, Q63P, Q64P, Q64PN