TROUBLESHOOTING
16.3 Actions to be Taken When the ERR. LED is On or Flashing
16
- 46
9
DE
V
ICE DE
S
CRIPT
IO
N
10
MU
LT
IPL
E
CP
U SY
S
T
EM
O
V
ER
VI
E
W
11
MUL
T
IP
L
E
CP
U
S
Y
S
TE
M
CONFIGURA
TION
12
CONCE
PT
OF MU
LT
IPL
E
CP
U SY
S
T
EM
13
COMMUN
ICA
TIO
N
S
BE
TWE
E
N
CP
U
MODUL
ES
14
P
A
RAM
E
TE
RS
A
DDE
D
F
O
R MU
LT
IP
LE
C
P
U
S
YSTE
M
S
15
ST
A
R
TIN
G A
M
U
LT
IPLE
CP
U
SYS
TEM
16
TR
O
U
B
L
E
S
HOOTING
(To the next page)
Error code
Error details and cause
Corrective action
2000
In the multiple CPU system, a CPU module incompatible with the
multiple CPU system is mounted.
Replace the incompatible CPU module with a compatible one.
The setting is different from the I/O module information input at power-
on.
(The I/O module mounting status was changed during operation. Or,
the module is almost disconnected.)
• Read the error information in C Controller setting utility, check the
module corresponding to the value (module No.), and replace the
module.
• If a GOT is connected to the main or extension base unit in a bus
topology, check the extension cable connection and the GOT
grounding status.
2100
In the I/O assignment parameter setting, the slot of the QI60 is set to
other than Intelli. (intelligent function module) and Interrupt (interrupt
module).
Correct the I/O assignment parameter setting.
• In the I/O assignment parameter setting, an I/O module is set as an
intelligent function module, or vice versa.
• In the I/O assignment parameter setting, a CPU module is set as
another module type or empty, or vice versa.
• In the I/O assignment parameter setting, the number of points set for
an intelligent function module is less than the actual number of
points.
• In the I/O assignment parameter setting, the switches were set for the
module than has no switch setting.
• Correct the I/O assignment parameters to match them to the actual
mounting status of intelligent function modules and CPU modules.
• In the I/O assignment parameter setting, remove the switch settings.
2103
• Two or more QI60 modules are mounted in the single CPU system.
• Two or more QI60/A1SI61 modules are mounted for the same control
CPU (programmable controller CPU only) in the multiple CPU
system.
• Two or more A1SI61 modules are mounted in the multiple CPU
system.
• Use one QI60 in the single CPU system.
• Change the number of QI60 modules set for the same control CPU to
only one in the multiple CPU system.
• Use only one A1SI61 in the multiple CPU system.
If an interrupt module is used for each QCPU in the multiple CPU
system, replace it with the QI60. (Use one A1SI61 and up to three
QI60 modules, or the QI60 modules only.)
Two or more QI60 modules with no interrupt pointer setting are
mounted.
• Use only one QI60.
• Configure the interrupt event settings for the QI60 modules other
than the first one.
2106
A total of five or more MELSECNET/H modules and/or CC-Link IE
controller network modules are mounted on the entire system.
Reduce the total number of MELSECNET/H modules and CC-Link IE
controller network modules on the entire system to four or less.
• Five or more MELSECNET/H modules are mounted.
• Five or more CC-Link IE controller network modules are mounted.
• Five or more Q series Ethernet modules are mounted.
• Reduce the number of MELSECNET/H modules to four or less.
• Reduce the number of CC-Link IE controller network modules to four
or less.
• Reduce the number of Q series Ethernet modules to four or less.
The same network No. or station No. is set for different networks or
stations on the MELSECNET/H or CC-Link IE controller network
system.
Check the network numbers or station numbers.
2107
The start X/Y set in the I/O assignment parameter setting is
overlapped with the one set for another module.
Correct the I/O assignment parameters to match them to the actual
mounting status of intelligent function modules.
2108
• A network module for the A2UCPU (A1SJ71LP21, A1SJ71BR11,
A1SJ71LR21, A1SJ71AP21, A1SJ71AR21, or A1SJ71AT21B) is
mounted.
• A network module for the Q2AS (A1SJ71QLP21(S), A1SJ71QBR11,
or A1SJ71QLR21) is mounted.
Replace the network module with a MELSECNET/H module.
2120
• In the single CPU system, the QA B or QA1S B base unit is used.
• In a multiple CPU system configuration, a C Controller module is set
as a CPU that controls modules on the QA B or QA1S B.
• Replace the base unit with the Q B.
• Set a High Performance model QCPU as a CPU that controls the
modules on the QA B or QA1S B.
2121
A CPU module is installed to other than the CPU slot and slot 0 to 2.
Check the slot position of the C Controller module and install the CPU
module in the correct slot.
2122
The QA1S B is used as the main base unit.
Change the main base unit to the Q B.
* 2 The CPU operation status after error occurrence can be set either to "Stop" or "Continue" in "Error time operation mode" in the <<System
settings>> tab of C Controller setting utility. (The LED indication also changes accordingly.)