![Mitsubishi Electric Q06CCPU-V User Manual Download Page 180](http://html.mh-extra.com/html/mitsubishi-electric/q06ccpu-v/q06ccpu-v_user-manual_1811831180.webp)
5
- 26
5.3 MELSECNET/H Module Access Function
5.3.4 Link device refresh setting
5
ACCESS VIA NETWORK MODULES
5) Actions for C Controller system malfunction
For a C Controller system malfunction or faulty user program processing
performance, take actions 1 to 3 if necessary to correct the system operation.
[Action 1: Increase the link device refresh cycle setting value.]
Check the total link device refresh time (Max.) measured during C Controller
system operation, in "Link device refresh time (Max.)" in the <<Module
information>> tab of either of the following utilities.
• MELSECNET/H utility
• CC IE Control utility
Re-set a link device refresh cycle appropriate to the confirmed link device
refresh time (Max.) so that the following relational expression is satisfied.
Also, since the C Controller system specifications must be satisfied, determine
the link device refresh cycle, taking into account the user program processing.
Figure 5.23 Corrective action 1
[Relational expression]
Measured link device refresh time (Max.) value < Link device refresh cycle
<Before taking
action>
C Controller
module processing
Increase link
device refresh
cycle.
Total link device refresh time
Link device
refresh cycle
<After taking
action>
Summary of Contents for Q06CCPU-V
Page 2: ......
Page 612: ...APPX 48 Appendix 11 Functions Added by Version Upgrade APPENDICES Memo ...
Page 617: ......