![Mitsubishi Electric Q06CCPU-V User Manual Download Page 491](http://html.mh-extra.com/html/mitsubishi-electric/q06ccpu-v/q06ccpu-v_user-manual_1811831491.webp)
16
TROUBLESHOOTING
16.2 Troubleshooting
16.2.11 When no LED on an output module turn on
16
- 20
9
DE
V
ICE DE
S
CRIPT
IO
N
10
MU
LT
IPL
E
CP
U SY
S
T
EM
O
V
ER
VI
E
W
11
MUL
T
IP
L
E
CP
U
S
Y
S
TE
M
CONFIGURA
TION
12
CONCE
PT
OF MU
LT
IPL
E
CP
U SY
S
T
EM
13
COMMUN
ICA
TIO
N
S
BE
TWE
E
N
CP
U
MODUL
ES
14
P
A
RAM
E
TE
RS
A
DDE
D
F
O
R MU
LT
IP
LE
C
P
U
S
YSTE
M
S
15
ST
A
R
TIN
G A
M
U
LT
IPLE
CP
U
SYS
TEM
16
TR
O
U
B
L
E
S
HOOTING
16.2.11
When no LED on an output module turn on
The following flowchart shows the procedures to be taken when no LED on an output
module turn on during C Controller system operation.
POINT
Before using the following flowchart, check if the RUN LED on the C Controller
module is on.
If the RUN LED is off, set the C Controller module to RUN to turn on the RUN
LED.
Figure 16.10 When no LED of an output module turn on
Q12DCCPU-V
Q06CCPU-V
Q06CCPU-V-B
Does the output
number match?
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
Is the MODE LED lit?
Is it on in <<Module information>>
of C Controller setting utility?
It is a hardware fault of the output
module.
Consult your local Mitsubishi service
center or representative, explaining the
details of the problem.
Change the output number.
Reexamine the user program.
No LEDs on an output module
turn on.
Does the LED turn
on when another output
module is forced to
turn on?
Does the
LED turn on when
the output module is replaced with
another output module and is
forced to turn on
again?
It is a hardware fault of the C Controller
module, base unit and/or extension
cable.
Consult your local Mitsubishi service
center or representative, explaining the
details of the problem.