252
Special operation and frequency control
<
Set point input calibration
>
1. Apply the input voltage of 0% set point setting (e.g. 0V) across terminals 2-5.
2. Enter in
C2 (Pr. 902)
the frequency which should be output by the inverter at the deviation of 0% (e.g. 0Hz).
3. In
C3 (Pr.902)
, set the voltage value at 0%.
4. Apply the voltage of 100% set point (e.g. 5V) to across terminals 2-5.
5. Enter in
Pr.125
the frequency which should be output by the inverter at the deviation of 100% (e.g. 60Hz).
6. In
C4 (Pr.903)
, set the voltage value at 100%.
<
Measured value calibration
>
1. Apply the input current of 0% measured value (e.g. 4mA) across terminals 4-5.
2. Make calibration using
C6 (Pr. 904)
.
3. Apply the input current of 100% measured value (e.g. 20mA) across terminals 4-5.
4. Make calibration using
C7 (Pr. 905)
.
The results of the above calibration are as shown below:
REMARKS
The frequency set in
C5 (Pr. 904)
and
Pr. 126
should be the same as set in
C2 (Pr. 902)
and
Pr. 125
.
NOTE
If the RH, RM, RL signal (multi-speed) or JOG signal (Jog operation) is entered with the X14 signal ON, PID control is
stopped and multi-speed or Jog operation started.
If the setting is as follows, PID control becomes invalid.
Pr. 79 Operation mode selection
="6" (switchover mode)
When the inverter is at a stop with
Pr. 261 Power failure stop selection
selected.
Changing the terminal function using any of
Pr. 178 to Pr. 184, Pr. 190 to Pr. 192
may affect the other functions. Set
parameters after confirming the function of each terminal.
When PID control is selected, the minimum frequency is the frequency set in
Pr. 902
and the maximum frequency is
the frequency set in
Pr. 903
.
Pr. 1 Maximum frequency
and
Pr. 2 Minimum frequency
settings are also valid.
The remote operation function is invalid during PID operation.
When the control is switched to PID control during normal
operation, the frequency command value calculated by PID
operation using 0Hz as standard is used without the
frequency during the operation.
Parameters referred to
Pr. 59 Remote function selection
Pr. 73 Analog input selection
Pr. 79 Operation mode selection
Pr. 178 to Pr. 184 (input terminal function selection)
Pr. 190 to Pr. 192 (output terminal function selection)
Pr. 261 Power failure stop selection
C2 (Pr. 902) to C7 (Pr. 905) Frequency setting voltage (current) bias/gain
100
0
0
5
(V)
(%)
[Set point setting]
100
0
0
20 (mA)
(%)
[Measured value]
4
60
0
0
100 Deviation (%)
[Manipulated variable]
Manipulated
variable (Hz)
PID action
Frequency
command
PID set point
Frequency command
during normal operation
ON
Operation when control is switched to PID control
during normal operation
PID operation
Normal
operation
Normal
operation