206
Selection of operation mode and operation location
(2) Selects the command source of the PU operation mode
(Pr. 551)
Any of the operation panel, PU connector, or USB connector can be specified as the command source in the PU operation
mode.
In the PU operation mode, set
Pr. 551
to "2" when executing parameter write, start command or frequency command
during the RS-485 communication with PU communication.
PU...PU operation mode, NET...network operation mode, —....without command source
∗1
The Modbus-RTU protocol cannot be used in the PU operation mode. When using the Modbus-RTU protocol, set
Pr. 550
to "2".
∗2
When the communication option is not fitted, the operation mode cannot be switched to the Network operation mode.
∗3
When
Pr. 551
= "9999", the priorities of the PU command source is USB connector
>
parameter unit (FR-PU04/FR-PU07)
>
operation panel.
NOTE
When performing the RS-485 communication with the PU connector when
Pr. 551
= "9999", PU mode command
source does not automatically change to the PU connector. Change to the Network operation mode to change the
command source.
When "2" (NET mode PU connector) is set in
Pr. 550
and "2" (PU mode PU connector) is set in
Pr, 551
, PU operation
mode has priority. When the communication option is not fitted, therefore, the operation mode cannot be switched to
the Network operation mode.
Changed setting value is valid when powering ON or resetting the inverter.
The Modbus-RTU protocol cannot be used in the PU operation mode. Select Network operation mode (NET mode
command source).
All of the operation mode indicator (
) of the operation panel turns OFF when command source is not
operation panel.
Pr. 550
Setting
Pr. 551
Setting
Command Source
Remarks
Operation
panel
USB
connector
PU connector
Communication
option
Parameter
unit
RS-485
communication
0
2
—
—
PU
PU
∗1
NET
∗2
3
—
PU
—
—
NET
∗2
4
PU
—
—
—
NET
∗2
9999
(initial
value)
PU
∗3
PU
PU
∗3
—
NET
∗2
2
2
—
—
PU
PU
∗1
—
Switching to NET
operation mode disabled
3
—
PU
—
NET
—
4
PU
—
—
NET
—
9999
(initial
value)
PU
∗3
PU
PU
∗3
NET
—
9999
(initial
value)
2
—
—
PU
PU
∗1
NET
∗2
3
—
PU
—
—
NET
∗2
Communication option
fitted
NET
—
Communication option
not fitted
4
PU
—
—
—
NET
∗2
Communication option
fitted
NET
—
Communication option
not fitted
9999
(initial
value)
PU
∗3
PU
PU
∗3
—
NET
∗2
Communication option
fitted
NET
—
Communication option
not fitted