![Mitsubishi Electric FR-E710W-0.1K Instruction Manual Download Page 218](http://html.mh-extra.com/html/mitsubishi-electric/fr-e710w-0-1k/fr-e710w-0-1k_instruction-manual_239797218.webp)
218
Communication operation and setting
4.20.4 Communication EEPROM write selection (Pr. 342)
When changing the parameter values frequently, set "1" in
Pr. 342
to write them to the RAM only.
The life of the EEPROM will be shorter if parameter write is performed frequently with the setting unchanged from "0 (initial
value)" (EEPROM write).
When parameter write is performed from the inverter PU connector, USB communication, and communication option,
parameters storage device can be changed from RAM to RAM only. Set when a frequent parameter
change is necessary.
Parameter
Number
Name
Initial Value
Setting Range
Description
342
Communication EEPROM
write selection
0
0
Parameter values written by communication are
written to the EEPROM and RAM.
1
Parameter values written by communication are
written to RAM.
The above parameters can be set when
Pr. 160 User group read selection
= "0". However, it can be set any time when the communication option is connected.
REMARKS
When "1" (write to RAM only) is set in
Pr. 342
, powering off the inverter will erase the changed parameter values. Therefore, the
parameter values available when power is switched on again are the values stored in EEPROM previously.