199
Selection of operation mode and operation location
(6) PU/External combined operation mode 1
(setting "3")
(7) PU/External combined operation mode 2
(setting "4")
Select the PU/External combined operation mode 1
when applying frequency command from the
operation panel or parameter unit (FR-PU04/FR-
PU07) and inputting the start command with the
external start switch.
Select "3" for
Pr. 79
. You cannot change to the other
operation mode.
When a frequency is applied from the external signal
by multi-speed setting, it has a higher priority than the
frequency command from the PU. When AU is ON,
the command signal to terminal 4 is used.
Select the PU/External combined operation mode 2 when
applying frequency command from the external
potentiometer, multi-speed or JOG signal and inputting the
start command by key operation of the operation panel or
parameter unit (FR-PU04/FR-PU07).
Select "4" for
Pr. 79
. You cannot change to the other
operation mode.
STR
Forward rotation
start
Reverse rotation
start
STF
SD
Inverter
Operation panel
Frequency setting
potentiometer
5
10
2
Inverter
Operation panel