Monitor display and monitor output signal
4.12.2 Monitor display selection of DU/PU and terminal FM
(Pr. 52, Pr. 54, Pr. 170, Pr. 171, Pr. 268, Pr. 563, Pr. 564)
(1) Monitor description list
(Pr. 52)
Set the monitor to be displayed on the operation panel and parameter unit (FR-PU04/FR-PU07) in
Pr. 52 DU/PU main
display data selection
.
Set the monitor to be output to the terminal FM (pulse train output) in
Pr. 54 FM terminal function selection
.
Refer to the following table and set the monitor to be displayed. (The monitor marked
×
cannot be selected.)
The monitor to be displayed on the main screen of the control panel and parameter unit (FR-PU04/FR-PU07) can be
selected.
In addition, signal to be output from the terminal FM (pulse train output) can be selected.
Parameter
Number
Name
Initial Value
Setting Range
Description
52
∗
DU/PU main display data
selection
0
(output
frequency)
0, 5, 7 to 12, 14, 20,
23 to 25, 52 to 57,
61, 62, 100
Select the monitor to be displayed on the
operation panel and parameter unit.
Refer to the following table for monitor
description.
54
∗
FM terminal function
selection
1
(output
frequency)
1 to 3, 5, 7 to 12,
14, 21, 24, 52, 53,
61, 62
Select the monitor output to terminal FM.
170
Watt-hour meter clear
9999
0
Set "0" to clear the watt-hour meter monitor.
10
Sets the maximum value for the monitoring
from communication to 9999kWh.
9999
Sets the maximum value for the monitoring
from communication to 65535kWh.
171
Operation hour meter clear
9999
0, 9999
Set "0" in the parameter to clear the operation
time monitor.
Setting 9999 does not clear.
268
∗
Monitor decimal digits
selection
9999
0
Displayed as integral value
1
Displayed in 0.1 increments.
9999
No function
563
Energization time carrying-
over times
0
0 to 65535
(reading only)
The numbers of cumulative energization time
monitor exceeded 65535h is displayed.
(Reading only)
564
Operating time carrying-
over times
0
0 to 65535
(reading only)
The numbers of operation time monitor
exceeded 65535h is displayed. (Reading only)
The above parameters can be set when
Pr. 160 User group read selection
= "0".
∗
This parameter allows its setting to be changed during operation in any operation mode even if "0" (initial value) is set in
Pr. 77 Parameter write selection
.
...... Specifications differ according to the date assembled.
to check the SERIAL number.
Types of Monitor
Unit
Pr. 52
Setting
Pr. 54
(FM)
Setting
Terminal FM
Full Scale Value
Description
Operation
panel
LED
PU
main
monitor
Output frequency
0.01Hz
0/100
1
Pr. 55
Displays the inverter output frequency.
Output current
0.01A
0/100
2
Pr. 56
Displays the inverter output current
effective value.
Output voltage
0.1V
0/100
3
100V, 200V
class
400V
Displays the inverter output voltage.
400V class 800V
Fault display
—
0/100
×
—
Displays 8 past faults individually.
Frequency setting
value
0.01Hz
5
∗1
5
Pr. 55
Displays the set frequency.
Motor torque
0.1%
7
∗1
7
Rated torque of the
applied motor
×
2
Displays the motor torque in % on the
assumption that the rated motor torque is
100%.
(Displays 0% during V/F control)