187
Misoperation prevention and parameter setting restriction
4.18.2 Parameter write disable selection (Pr. 77)
(1) Write parameters only during stop
(setting "0" initial value)
Parameters can be written only during a stop in the PU operation mode.
The shaded parameters in the parameter list
(page 62)
can always be written regardless of the operation mode and
operating status. However,
Pr. 72 PWM frequency selection, Pr. 240 Soft-PWM operation selection,
and
Pr. 275 Stop-on contact
excitation current low-speed multiplying factor
can be written when the inverter is running in the PU operation mode, but
cannot be written in the External operation mode.
(2) Inhibit parameter write
(setting "1")
(3) Write parameters during operation
(setting "2")
Parameters can always be written.
The following prameters cannot be written when the inverter is running if
Pr. 77
= "2". Stop the inverter when changing their
parameter settings.
You can select whether write to various parameters can be performed or not. Use this function to prevent parameter
values from being rewritten by misoperation.
Parameter
Number
Name
Initial Value
Setting Range
Description
77
Parameter write selection
0
0
Write is enabled only during a stop.
1
Parameter can not be written.
2
Parameter write is enabled in any operation
mode regardless of operation status.
The above parameters can be set when
Pr. 160
User group read selection
= "0".
Pr. 77
can be always set independently of the operation mode and operation status.
.............Specifications differ according to the date assembled.
to check the SERIAL number.
Parameter write is not enabled.
(Read is enabled.)
Parameter clear and all parameter clear cannot be
performed, either.
The parameters given on the right can be written if
Pr. 77
=
"1".
Parameter
Number
Name
22
Stall prevention operation level
75
Reset selection/disconnected PU detection/
PU stop selection
77
Parameter write selection
79
Operation mode selection
160
User group read selection
296
Password lock level
297
Password lock/unlock
Parameters referred to
Pr. 79 Operation mode selection
Parameter
Number
Name
23
Stall prevention operation level compensation
factor at double speed
40
RUN key rotation direction selection
48
Second stall prevention operation current
60
Energy saving control selection
61
Reference current
66
Stall prevention operation reduction starting
frequency
71
Applied motor
79
Operation mode selection
80
Motor capacity
81
Number of motor poles
82
Motor excitation current
83
Rated motor voltage
84
Rated motor frequency
90 to 94
(Motor constants)
96
Auto tuning setting/status
178 to 184
(input terminal function selection)
190 to 192
(output terminal function selection)
277
Stall prevention operation current switchover
292
Automatic acceleration/deceleration
293
Acceleration/deceleration separate selection
298
Frequency search gain
329
Digital input unit selection
(Parameter for the plug-in option FR-A7AX E kit)
450
Second applied motor
541
Frequency command sign selection (CC-Link)
(Parameter for the plug-in option FR-A7NC E kit)
800
Control method selection
859
Torque current
Parameter
Number
Name