Frequency setting by analog input (terminal 2, 4)
4.17 Frequency setting by analog input (terminal 2, 4)
4.17.1 Analog input selection (Pr. 73, Pr. 267)
(1) Selection of analog input specifications
For the terminal 2 for analog voltage input, 0 to 5V (initial value) or 0 to 10V can be selected.
Either voltage input (0 to 5V, 0 to 10V) or current input (4 to 20mA initial value) can be selected for terminal 4 used for
analog input.
Change the input specifications to change
Pr. 267
and voltage/current input switch.
Rated specifications of terminal 4 change according to the voltage/current input switch setting.
Voltage input: Input resistance 10k
Ω
±
1k
Ω
, maximum permissible input voltage 20VDC
Current input: Input resistance 233
Ω
±
5
Ω
, maximum permissible input voltage 30mA
Purpose
Parameter that should be Set
Refer to Page
Selection of voltage/current input
(terminal 2, 4)
Perform forward/reverse rotation by
analog input.
Analog input selection
Pr. 73, Pr. 267
Adjustment (calibration) of analog
input frequency and voltage (current)
Bias and gain of frequency
setting voltage (current)
Pr. 125, Pr. 126, Pr. 241,
C2 to C7 (Pr. 902 to Pr. 905)
You can select the function that switches between forward rotation and reverse rotation according to the analog input
terminal specifications and input signal.
Parameter
Number
Name
Initial
Value
Setting
Range
Description
73
Analog input
selection
1
0
Terminal 2 input 0 to 10V
Without reversible
operation
1
Terminal 2 input 0 to 5V
10
Terminal 2 input 0 to 10V
With reversible
operation
11
Terminal 2 input 0 to 5V
267
Terminal 4 input
selection
0
Voltage/current input switch
Description
Standard control
circuit terminal model
Safety stop function
model
0
Terminal 4 input 4 to
20mA
1
Terminal 4 input 0 to 5V
2
Terminal 4 input 0 to
10V
The above parameters can be set when
Pr. 160 User group read selection
= "0".
Standard control circuit terminal model
Safety stop function model
Current input (initial setting)
Voltage input
Control circuit terminal block
Current input (initial setting)
Voltage input