155
Monitor display and monitor output signal
Converter output
voltage
0.1V
8
∗1
8
100V, 200V
class
400V
Displays the DC bus voltage value.
400V class 800V
Regenerative brake
duty
0.1%
9
∗1
9
Pr. 70
Brake duty set in
Pr. 30, Pr. 70
Electronic thermal
relay function load
factor
0.1%
10
∗1
10
100%
Displays the thermal cumulative value on
the assumption that the thermal operation
level is 100% (Larger thermal between the
motor thermal and transistor thermal).
Output current peak
value
0.01A
11
∗1
11
Pr. 56
Holds and displays the peak value of the
output power monitor.
(Cleared at every start)
Converter output
voltage peak value
0.1V
12
∗1
12
100V, 200V
class
400V Holds and displays the peak value of the
DC bus voltage value.
(Cleared at every start)
400V class 800V
Output power
0.01kW
14
∗1
14
Rated inverter
power
×
2
Displays the power on the inverter output
side
Input terminal status
—
—
∗1
×
—
Displays the input terminal ON/OFF status
on the PU.
(
for DU display)
Output terminal
status
—
—
∗1
×
—
Displays the output terminal ON/OFF
status on the PU.
(
for DU display)
Cumulative
energization time
1h
20
×
—
Adds up and displays the energization time
after inverter shipment.
You can check the numbers of the monitor
value exceeded 65535h with
Pr. 563
.
Reference voltage
output
—
—
21
—
Terminal FM:
Output 1440pulse/s
Actual operation time
,
1h
23
×
—
Adds up and displays the inverter operation
time.
You can check the numbers of the monitor
value exceeded 65535h with
Pr. 564
.
Can be cleared by
Pr. 171
.
Motor load factor
0.1%
24
24
200%
Displays the output current value on the
assumption that the inverter rated current
value is 100%.
Monitor value = output power monitor
value/rated inverter current 100 [%]
Cumulative power
0.01kWh
25
×
—
Adds up and displays the power amount
based on the output power monitor.
Can be cleared by
Pr. 170
.
PID set point
0.1%
52
52
100%
Displays the set point, measured value and
deviation during PID control (
for details)
PID measured value
0.1%
53
53
100%
PID deviation
0.1%
54
×
—
Inverter I/O terminal
monitor
—
55
×
×
—
Displays the ON/OFF status of the inverter
input terminal and output terminal on the
operation panel (
for
details)
Option input terminal
status
—
56
×
×
—
Displays the input terminal ON/OFF status
of the digital input option (FR-A7AX E Kit)
on the operation panel. (
for details)
Option output
terminal status
—
57
×
×
—
Displays the output terminal ON/OFF
status of the digital output option (FR-A7AY
E kit) or relay output option (FR-A7AR E
Kit) on the operation panel (
for details).
Types of Monitor
Unit
Pr. 52
Setting
Pr. 54
(FM)
Setting
Terminal FM
Full Scale Value
Description
Operation
panel
LED
PU
main
monitor