Check first when you have a trouble
5.5.8
Speed varies during operation
When Advanced magnetic flux vector control or the slip compensation is selected, the output frequency varies between 0 and
2Hz as load fluctuates. This is a normal operation and not a fault.
5.5.9
Operation mode is not changed properly
Check
points
Possible Cause
Countermeasures
Refer
to
page
Input
signal
Multi-speed command signal is chattering.
Take countermeasures to suppress chattering.
—
Load
Load varies during an operation.
Select Advanced magnetic flux vector control or
General-purpose magnetic flux vector control.
Input
signal
Frequency setting signal is varying.
Check the frequency setting signal.
—
The frequency setting signal is affected by EMI.
Set filter to the analog input terminal using
Pr. 74 Input
filter time constant
.
Take countermeasures against EMI, such as using
shielded wires for input signal lines.
Malfunction is occurring due to the undesirable current
generated when the transistor output unit is connected.
Use terminal PC (terminal SD when source logic) as a
common terminal to prevent a malfunction caused by
undesirable current.
Parameter
Setting
Pr. 80 Motor capacity
and
Pr. 81 Number of motor poles
setting is improper for the capacities of the inverter and
the motor for Advanced magnetic flux vector control or
General-purpose magnetic flux vector control.
Check the
Pr. 80 Motor capacity
and
Pr. 81 Number of
motor poles
setting.
Fluctuation of power supply voltage is too large.
Change the
Pr. 19 Base frequency voltage
setting (about
3%) under V/F control.
Hunting occurs by the generated vibration, for example,
when structural rigidity at load side is insufficient.
Disable automatic control functions, such as energy
saving operation, fast-response current limit function,
regeneration avoidance function, Advanced magnetic
flux vector control, General-purpose magnetic flux
vector control, and stall prevention.
During the PID control, set smaller values to
Pr.129 PID
proportional band
and
Pr.130 PID integral time
.
Lower the control gain, and adjust to increase the
stability.
—
Change
Pr. 72 PWM frequency selection
setting.
Others
Wiring length exceeds 30m when Advanced magnetic
flux vector control or General-purpose magnetic flux
vector control is performed.
Perform offline auto tuning.
Wiring length is too long for V/F control, and a voltage
drop occurs.
Adjust
Pr. 0 Torque boost
by increasing with 0.5%
increments for low-speed operation.
Change to Advanced magnetic flux vector control or
General-purpose magnetic flux vector control.
Check
points
Possible Cause
Countermeasures
Refer
to
page
Input
signal
Start signal (STF or STR) is ON.
Check that the STF and STR signals are OFF.
When either is ON, the operation mode cannot be
changed.
Parameter
Setting
Pr. 79
setting is improper.
When
Pr. 79 Operation mode selection
setting is "0" (initial
value), the inverter is placed in the External operation mode
at input power ON. To switch to the PU operation mode,
press
on the operation panel (press
when the
parameter unit (FR-PU04/FR-PU07) is used). At other
settings (1 to 4, 6, 7), the operation mode is limited
accordingly.
Operation mode and a writing device do not
correspond.
Check
Pr. 79, Pr. 338, Pr. 339, Pr. 550, Pr. 551,
and select
an operation mode suitable for the purpose.