Function assignment of external terminal and control
4.11 Function assignment of external terminal and control
4.11.1 Input terminal function selection (Pr. 178 to Pr. 184)
The above parameters can be set when
Pr. 160 User group read selection
= "0".
∗1
The setting value of "60" is available for
Pr. 178
only.
∗2
The setting value of "61" is available for
Pr. 179
only.
∗3
For the safety stop function model, this setting is active only during the communication operation. (
(1) Input terminal function assignment
Using
Pr. 178 to Pr. 184
, set the functions of the input terminals.
Refer to the following table and set the parameters:
Purpose
Parameter that should be Set
Refer to Page
Assign function to input terminal
Input terminal function
selection
Pr. 178 to Pr. 184
Set MRS signal (output shutoff) to
NC contact specification
MRS input selection
Pr. 17
Assign start signal and forward/
reverse command to other signals
Start signal (STF/STR)
operation selection
Pr. 250
Assign function to output terminal
Output terminal function
assignment
Pr. 190 to Pr. 192
Detect output frequency
Up-to-frequency
sensitivity
Output frequency
detection
Pr. 41 to Pr. 43
Detect output current
Output current detection
Zero current detection
Pr. 150 to Pr. 153
Remote output function
Remote output
Pr. 495 to Pr. 497
Use these parameters to select/change the input terminal functions.
Parameter
Number
Name
Initial
Value
Initial Signal
Setting Range
178
STF terminal function
selection
60
STF (forward rotation command)
0 to 5, 7, 8, 10, 12, 14 to 16, 18,
24, 25, 60
, 61
, 62, 65 to 67,
9999
179
STR terminal function
selection
61
STR (reverse rotation command)
180
RL terminal function
selection
0
RL (low-speed operation command)
181
RM terminal function
selection
1
RM (middle speed operation
command)
182
RH terminal function
selection
2
RH (high-speed operation
command)
183
MRS terminal function
selection
24
MRS (output stop)
184
RES terminal function
selection
62
RES (inverter reset)
Setting
Signal
Function
Related Parameters
Refer to
Page
0
RL
Pr. 59
= 0 (initial value)
Low-speed operation command
Pr. 4 to Pr. 6, Pr. 24 to Pr. 27
Pr.232 to Pr.239
Pr. 59
= 1, 2
Remote setting (setting clear)
Pr. 59
Pr. 270
= 1
∗2
Stop-on contact selection 0
Pr. 270, Pr. 275, Pr. 276
1
RM
Pr. 59
= 0 (initial value)
Middle-speed operation command
Pr. 4 to Pr. 6, Pr. 24 to Pr. 27,
Pr. 232 to Pr. 239
Pr. 59
= 1, 2
Remote setting (deceleration)
Pr. 59
2
RH
Pr. 59
= 0 (initial value)
High-speed operation command
Pr. 4 to Pr. 6, Pr. 24 to Pr. 27,
Pr. 232 to Pr. 239
Pr. 59
= 1, 2
Remote setting (acceleration)
Pr. 59