150
Function assignment of external terminal and control
4.11.7 Output current detection function (Y12 signal, Y13 signal, Pr. 150 to Pr. 153)
The above parameters can be set when
Pr.
160 User group read selection
= "0".
The output current during inverter running can be detected and output to the output terminal.
Parameter
Number
Name
Initial Value
Setting
Range
Description
150
Output current detection
level
150%
0 to 200%
100% is the rated inverter current.
151
Output current detection
signal delay time
0s
0 to 10s
Output current detection period.
The time from when the output current has risen
above the setting until the output current detection
signal (Y12) is output.
152
Zero current detection
level
5%
0 to 200%
The rated inverter current is assumed to be 100%.
153
Zero current detection
time
0.5s
0 to 1s
Period from when the output current drops below the
Pr. 152
value until the zero current detection signal
(Y13) is output.
(1) Output current detection
(Y12 signal,
Pr. 150, Pr. 151
)
The output current detection function can be used for
excessive torque detection, etc.
If the output current remains higher than the
Pr. 150
setting
during inverter operation for longer than the time set in
Pr.
151
, the output current detection signal (Y12) is output from
the inverter's open collector or relay output terminal.
When the Y12 signal turns ON, the ON state is held for
approximately 100ms.
For the Y12 signal, set "12 (positive logic) or 112 (negative
logic)" in
Pr. 190 to Pr. 192 (output terminal function selection)
and assign functions to the output terminal.
(2) Zero current detection (Y13 signal,
Pr. 152, Pr. 153
)
If the output current remains lower than the
Pr. 152
setting
during inverter operation for longer than the time set in
Pr.
153
, the zero current detection (Y13) signal is output from the
inverter's open collector or relay output terminal.
When the inverter's output current falls to "0", torque will not
be generated. This may cause a drop due to gravity when
the inverter is used in vertical lift application.
To prevent this, the Y13 signal can be output from the
inverter to close the mechanical brake when the output
current has fallen to "zero".
For the Y13 signal, set "13 (positive logic) or 113 (negative
logic)" in
Pr. 190 to Pr. 192 (output terminal function selection)
and assign functions to the output terminal.
REMARKS
This function is also valid during execution of the offline auto tuning.
The response time of Y12 and Y13 signals is approximately 0.1s. Note that the response time changes according to the load
condition.
When
Pr. 152
= "0", detection is disabled.
NOTE
Changing the terminal assignment using
Pr. 190 to Pr. 192 (output terminal function selection)
may affect the other
functions. Set parameters after confirming the function of each terminal.
Time
Pr. 150
OFF
ON
OFF
Output current
detection signal
(Y12)
100ms
Output current
Pr. 151
OFF
ON
Start signal
Time
Output current
OFF
ON
Zero current
detection time
(Y13)
Pr. 153
Detection time
Pr. 153
Detection time
Pr. 152
OFF
ON
0[A]
100ms
∗
Pr. 152
∗
The zero current detection signal (Y13) holds the
signal for approximately 100ms once turned ON.