129
Motor brake and stop operation
REMARKS
For the 5.5K, 7.5K, when the
Pr. 12
setting is the following, changing the
Pr. 71 Applied motor
setting automatically changes the
Pr. 12
setting. Therefore, it is not necessary to change the
Pr. 12
setting.
(a) When 4% (initial value) is set in
Pr. 12
The
Pr. 12
setting is automatically changed to 2% if the
Pr. 71
value is changed from the value selecting the standard motor
(0, 3 to 6, 23, 24, 40, 43, 44) to the value selecting the constant-torque motor (1, 13 to 16, 50, 53, 54).
(b) When 2% is set in
Pr. 12
The
Pr. 12
setting is automatically changed to 4% (initial value) if the
Pr. 71
value is changed from the value selecting the
constant-torque motor (1, 13 to 16, 50, 53, 54) to the value selecting the standard motor (0, 3 to 6, 23, 24, 40, 43, 44).
Even if the
Pr. 12
setting is increased, braking torque is limited so that the output current is within the rated inverter current.
CAUTION
As stop holding torque is not produced, install a mechanical brake.
Parameters referred to
Pr. 13 Starting frequency
Pr. 71 Applied motor