172
Operation setting at fault occurrence
4.14.2 Input/output phase loss protection selection (Pr. 251, Pr. 872)
(1) Output phase loss protection selection
(Pr. 251)
If phase loss occurs during inverter running (except for during DC brake operation, or output frequency is 1Hz or less),
output phase loss protection (E.LF) activates, and inverter trips.
When
Pr. 251
is set to "0", output phase loss protection (E.LF) becomes invalid.
(2) Input phase loss protection selection
(Pr. 872)
When
Pr. 872
is set to "1", input phase loss protection (E.ILF) is provided if a phase loss of one phase among the three
phases is detected for 1s continuously.
4.14.3 Earth (ground) fault detection at start (Pr. 249)
You can choose whether to make Input/output phase loss protection valid or invalid.
Output phase loss protection is a function to stop the inverter output if one of the three phases (U, V, W) on the
inverter's output side (load side) is lost.
Input phase loss protection is a function to stop the inverter output if one of the three phases (R/L1, S/L2, T/L3) on the
inverter's input side is lost.
Parameter
Number
Name
Initial Value
Setting Range
Description
251
Output phase loss
protection selection
1
0
Without output phase loss protection
1
With output phase loss protection
872
∗
Input phase loss protection
selection
1
0
Without input phase loss protection
1
With input phase loss protection
The above parameters can be set when
Pr. 160 User group read selection
= "0".
∗
Available only for the three-phase power input model.
NOTE
If an input phase loss continues for a long time, the converter section and capacitor lives of the inverter will be
shorter.
If the load is light or during a stop, lost phase cannot be detected because detection is performed based on the
fluctuation of bus voltage. Large unbalanced phase-to-phase voltage of the three-phase power supply may also
cause input phase loss protection (E.ILF).
Phase loss can not be detected during regeneration load operation.
If parameter copy is performed from single-phase power input model to three-phase power input model,
Pr. 872
setting may be changed. Check
Pr. 872
setting after parameter copy.
You can choose whether to make earth (ground) fault detection at start valid or invalid. Earth (Ground) fault detection is
executed only right after the start signal is input to the inverter.
Protective function will not activate if an earth (ground) fault occurs during operation.
Parameter
Number
Name
Initial Value
Setting Range
Description
249
Earth (ground) fault
detection at start
0
0
Without earth (ground) fault detection
1
With earth (ground) fault detection
The above parameters can be set when
Pr. 160 User group read selection
= "0".
NOTE
As detection is executed at start, output is delayed for approx. 20ms every start.
If an earth (ground) fault is detected with "1" set in
Pr. 249
, output side earth (ground) fault overcurrent (E.GF) is detected and
the inverter trips. (
If the motor capacity is smaller than the inverter capacity of the 5.5K or more, earth (ground) fault detection may not be
provided.