Causes and corrective actions
Operation panel
indication
E.OV1
FR-PU04
FR-PU07
OV During Acc
Name
Regenerative overvoltage trip during acceleration
Description
If regenerative energy causes the inverter's internal main circuit DC voltage to reach or exceed the specified value,
the protective circuit is activated and the inverter trips. The circuit may also be activated by a surge voltage produced
in the power supply system.
Check point
Check for too slow acceleration. (e.g. during downward acceleration in vertical lift load)
Check that the setting of
Pr. 22
Stall prevention operation level
is not too small.
Corrective action
Decrease the acceleration time.
Check that regeneration avoidance function
(Pr. 882, Pr. 883, Pr. 885, Pr. 886)
is used.
Set the
Pr.22 Stall prevention operation level
correctly.
Operation panel
indication
E.OV2
FR-PU04
FR-PU07
Stedy Spd OV
Name
Regenerative overvoltage trip during constant speed
Description
If regenerative energy causes the inverter's internal main circuit DC voltage to reach or exceed the specified value,
the protective circuit is activated to stop the inverter output. The circuit may also be activated by a surge voltage
produced in the power supply system.
Check point
Check for sudden load change.
Check that the setting of
Pr. 22
Stall prevention operation level
is not too small.
Corrective action
Keep load stable.
Check that regeneration avoidance function
(Pr. 882, Pr. 883, Pr. 885, Pr. 886)
is used.
Use the brake resistor, brake unit or power regeneration common converter (FR-CV) as required.
Set the
Pr.22 Stall prevention operation level
correctly.
Operation panel
indication
E.OV3
FR-PU04
FR-PU07
OV During Dec
Name
Regenerative overvoltage trip during deceleration or stop
Description
If regenerative energy causes the inverter's internal main circuit DC voltage to reach or exceed the specified value,
the protective circuit is activated to stop the inverter output. The circuit may also be activated by a surge voltage
produced in the power supply system.
Check point
Check for sudden speed reduction.
Corrective action
Increase the deceleration time. (Set the deceleration time which matches the moment of inertia of the load)
Longer the brake cycle.
Use regeneration avoidance function
(Pr. 882, Pr. 883, Pr. 885, Pr. 886)
.
Use the brake resistor, brake unit or power regeneration common converter (FR-CV) as required.
Operation panel
indication
E.THT
FR-PU04
FR-PU07
Inv. Overload
Name
Inverter overload trip (electronic thermal relay function)
Description
If the temperature of the output transistor element exceeds the protection level under the condition that a current not
less than the rated inverter current flows and overcurrent trip does not occur (230% or less), the electronic thermal
relay activates to stop the inverter output. (Overload capacity 150% 60s, 200% 3s)
Check point
Check that acceleration/deceleration time is not too short.
Check that torque boost setting is not too large (small).
Check that load pattern selection setting is appropriate for the load pattern of the using machine.
Check the motor for use under overload.
Check for too high surrounding air temperature.
Corrective action
Increase acceleration/deceleration time.
Adjust the torque boost setting.
Set the load pattern selection setting according to the load pattern of the using machine.
Reduce the load weight.
Set the surrounding air temperature to within the specifications.