FR-E500 series operation panel (PA02) setting
4.24.2 Bias and gain of the built-in frequency setting potentiometer (C22 (Pr. 922) to C25
(Pr. 923))
Adjust the bias of the potentiometer of the operation panel
using
Pr. 922 (C22, C23)
and gain with
Pr. 923 (C24, C25)
.
<Setting>
[Setting from the FR-E500 series operation panel (PA02)]
Bias/gain adjustment methods using the built-in potentiometer are shown below.
Method to adjust any point by turning the potentiometer.
Method to adjust any point without turning the potentiometer.
Method to adjust the bias/gain frequency only.
When the operation panel (PA02) for the FR-E500 series is hooked up with the PU cable, the magnitude (slope) of the
output frequency to the frequency setting potentiometer of the operation panel can be set as desired.
Parameter
No.
Name
Initial
Value
Setting
Range
Description
C22(922)
∗1
Frequency setting voltage bias
frequency (built-in potentiometer)
0Hz
0 to 400Hz
Frequency on the bias side of PA02 built-in
frequency setting potentiometer.
C23(922)
∗1
Frequency setting voltage bias (built-
in potentiometer)
0%
0 to 300%
Converted % of the bias side setting level of
PA02 built-in frequency setting potentiometer.
C24(923)
∗1
Frequency setting voltage gain
frequency (built-in potentiometer)
60Hz
0 to 400Hz
Frequency on the gain side of PA02 built-in
frequency setting potentiometer.
C25(923)
∗1
Frequency setting voltage gain (built-
in potentiometer)
100%
0 to 300%
Converted % of the bias side setting level of
PA02 built-in frequency setting potentiometer.
∗1
The parameter number in parentheses is the one for use with the operation panel (PA02) for the FR-E500 series or parameter unit (FR-PU04/FR-PU07).
The above parameters can be set when
Pr. 160 User group read selection
="0".
Power on
Make sure that the inverter is in PU mode.
Read
Pr. 923
to display the currently set gain frequency.
Set the gain frequency in
Pr. 923
to display the analog voltage value of the built-in frequency setting
potentiometer in %.
Method to adjust any
point by turning the
potentiometer.
Method to adjust only
the gain frequency and
not to adjust the
voltage
Method to adjust any
point without turning
the potentiometer.
Press the
key to shift to the next parameter
Re-set the
Pr.79 Operation mode selection
value according to the operation mode being used.
Output frequency (Hz)
60Hz
0
C23 (Pr. 922
)
Frequency setting signal
(Built-in frequency setting potentiometer)
100%
C25 (Pr. 923)
Initial value
Bias
C22 (
Pr. 922
)
Gain
C24 (Pr. 923)