282
FR-E500 series operation panel (PA02) setting
[Setting with the inverter operation panel without fitting the FR-E500 series operation panel (PA02)]
a) Method to adjust any point
(to change to 80% from 100%)
Operation Display
1.
Confirm the RUN indication and operation mode
indication
The inverter should be at a stop.
The inverter should be in the PU operation mode
(depends on
).
2.
Press
to choose the parameter setting
mode.
3.
Turn
until
appears.
4.
Press
until
appears.
5.
Turn
until
appears.Turn the dial to
C25 (Pr. 923) Frequency setting voltage gain (built-in
potentiometer)
6.
Press
to show the analog voltage value
(%).
7.
Turn
to set gain voltage (%).
"minimum value of the potentiometer is 0%,
maximum value is 100%"
8.
Press
to set.
Flicker Parameter setting complete!!
(Adjustment completed)
Turn
to read another parameter.
Press
to return to the
indication (step 4).
Press
twice to show the next parameter (
).
REMARKS
By pressing
after step 6, you can confirm the current frequency setting bias/gain setting.
It cannot be confirmed after execution of step 7.
The parameter
number read
previously appears.
C0 to C25 setting
is enabled.
Hz
A
Analog voltage value (%) of built-
in frequency setting potentiometer
Hz
A
The gain frequency is reached
when analog voltage value
(%) of built-in frequency
setting potentiometer is 80%.
REMARKS
The current setting at the instant of turning
is displayed.