External input/output functions
Dedicated input/output
6-559
6.3
Dedicated input/output
The functions shown in
are available for the dedicated input/output signals. These are used by the
parallel input/output unit by assigning the signal No. in the parameter.
The signal No. is assigned by the signal No. used in the order of "input signal" and "output signal" in each
parameter. Refer to
Page 83, "3.15 Operation of parameter screen"
for details on setting the parameters. If
a "-1" is designated for the assigned signal No., that signal will be invalidated.
The I/O parameters can be set on the T/B parameter screen or by using the maintenance tool of the PC sup-
port software (optional). And refer to
Page 580, "6.5.2 Timing chart example"
for time chart.
To use the dedicated I/O signals, set the controller mode to AUTOMATIC, and turn on the operation rights
input signal (IOENA) beforehand.
Table 6-6:Table of dedicated input/output
Parameter
name
Class
Name
Function
Signal
level
Note1)
Factory shipment signal number.
Input, output
CR7xx-Q
CR7xx-D
RCREADY
Input
-
-
-1(No meaning),
10001
-1(No meaning),
-1
Output Controller power ON
ready
Outputs that the power has been turned ON
and that the external input signal can be
received.
ATEXTMD
Input
-
-
-1(No meaning),
10002
-1(No meaning),
-1
Output Remote mode output
This output indicates that the controller mode
is set to AUTOMATIC and remote operation
mode.
This signal must be turned ON before any con-
trol tasks using I/O signals can be performed.
TEACHMD
Input
-
-
-1(No meaning),
10003
-1(No meaning),
-1
Output Teaching mode output This output indicates that the controller mode
is set to Teaching mode.
ATTOPMD
Input
-
-
-1(No meaning),
10004
-1(No meaning),
-1
Output Automatic mode output This output indicates that the controller mode
is set to AUTOMATIC and local operation
mode.
IOENA
Input
Operation rights input
signal
Sets the validity of the operation rights for the
external signal control.
Level 10005,
10005
5,
3
Output Operation rights output
signal
Outputs the operation rights valid state for the
external signal control.
The operation right is given when the opera-
tion right input signal is ON, the controller
mode is set to AUTOMATIC, and there is no
other device that currently has the operation
right.
START
(Operation
right
required)
Input
Start input
This input starts a program. To start a specific
program, select the program using the pro-
gram selection signal "PRGSEL" and numeri-
cal input "IODATA," and then input the start
signal. Note that when the parameter "PST" is
enabled, the system reads the program num-
ber from the numerical input (IODATA) and
starts the corresponding program (i.e., pro-
gram selection becomes no longer neces-
sary).
All task slots are executed during multitask
operation.
However, slots whose starting condition is set
to ALWAYS or ERROR via a parameter "SLT*"
will not be executed.
Edge 10006,
10006
3,
0
Output Operating output
This output indicates that a program is being
executed. During multitask operation, this sig-
nal turns ON when at least one task slot is
operating.
However, slots whose starting condition is set
to ALWAYS or ERROR via a parameter "SLT*"
will not be executed.