Chapter 9 User interfaces
9.2.1.3.2 Config
Reader type
Elster Grey Snapfit (4 ms)
Elster reader
Minimum signal length for the signal detection: 4 ms
sample interval: 1ms
sample time: 30µs
Elster Black Snapfit (4 ms)
Elster T. PROBE (4 ms)
Elster LRP (4 ms)
Elster Q4000 (4 ms)
Elster HRP (4 ms)
Elster ODO7 (4 ms)
Elster HELIX 4000 (4 ms)
Elster PR7 (4 ms)
Elster PR6 (4 ms)
Elster reader
Minimum signal length for the signal detection: 4 ms
sample interval: 1ms
sample time: 40µs
Itron CYBLE K1000 (64 ms)
Itron reader
Minimum signal length for the signal detection: 64 ms
sample interval: 15,6ms
sample time: 30µs
Itron EMES UNIT (64 ms)
Sensus HRI (15 ms)
Sensus reader
Minimum signal length for the signal detection: 15 ms
sample interval: 1ms
sample time: 30µs
Sensus HRI-Mei (15 ms)
Sensus OD01 (4 ms)
Sensus reader
Minimum signal length for the signal detection: 4 ms
sample interval: 1ms
sample time: 30µs
Sensus RD01 (4 ms)
Arad BASIC (4 ms)
Arad reader
Minimum signal length for the signal detection: 4 ms
sample interval: 1ms
sample time: 30µs
Arad 40/50 (4 ms)
Selection of the reader type
Rev. 01