DC and surge test voltages
138 Baker DX 71-030 User Guide EN V10
www.megger.com
Table 8. NEMA MG-1/EASA AR100 DC-HiPot.
V Line
Per Unit
New, 3.4 × V Line + 1,700
In Service, 65% of New
480
392
3,332
2,165.8
575
469
3,655
2,375.75
600
490
3,740
2,431
2,300
1,878
9,520
6,188
4,160
3,397
15,844
10,298.6
6,900
5,634
25,160
16,354
13,800
11,268
48,620
31,603
Table 9. IEEE 522 Surge testing.
V Line
Per Unit
New, 3.5 × Per Unit
In Service, 75% of New
480
392
1,372
1,029
575
469
1,642
1,232
600
490
1,715
1,286
2,300
1,878
6,573
4,930
4,160
3,397
11,890
8,917
6,900
5,634
19,719
14,789
13,800
11,268
39,438
29,578
Table 10. IEC 34-15.
V Line
Per Unit
V Line × 4E + 5,000
0.2 us, 65%
480
392
6,920
4,498
575
469
7,300
4,745
600
490
7,400
4,810
2,300
1,878
14,200
9,230
4,160
3,397
21,640
14,066
6,900
5,634
32,600
21,190
13,800
11,268
60,200
39,130
Summary of Contents for Baker DX
Page 1: ......
Page 2: ......
Page 10: ...Table of Contents viii Baker DX 71 030 User Guide EN V10 www megger com...
Page 28: ...Baker DX Instrument Overview 18 Baker DX 71 030 User Guide EN V10 www megger com...
Page 38: ...Baker DX User Interface Overview 28 Baker DX 71 030 User Guide EN V10 www megger com...
Page 58: ...Setting up the Baker DX Tester 48 Baker DX 71 030 User Guide EN V10 www megger com...
Page 149: ...megger com 139 RIC Templates Figure 141 RIC template 1...
Page 150: ...RIC templates 140 Baker DX 71 030 User Guide EN V10 www megger com Figure 142 RIC template 2...
Page 155: ...Index megger com 145...
Page 156: ...megger com 146...