Procedures for Testing with the DX Host
84 Baker DX 71-030 User Guide EN V10
www.megger.com
7.
Observe the new relative positions of the PD signal and the threshold line. If the two are
not at an equivalent level, enter into maintenance mode again and re-adjust the user
setting
PD threshold (mV).
Figure 91. User Settings screen, PD settings.
8.
Record the level of the threshold in the
Detection System Sens
user setting—this is the
system level noise. You will likely notice this noise as small points registering just under
the waveform (within the threshold bars) as shown in the example excerpt below.
Figure 92. Example of system level noise.
9.
This information will be reported with partial discharge tests that are saved along with
the date the sensitivity was last recorded. Press the
PD/Temp Settings
button then the
Detection System Sensitivity
button in the popup menu to change this value.
10.
If needed, re-adjust the
PD threshold (mV)
so that it is above the detected noise floor
so that only PD will trip the event indicator. The DSS value must always be lower than
the PD threshold value.
Summary of Contents for Baker DX
Page 1: ......
Page 2: ......
Page 10: ...Table of Contents viii Baker DX 71 030 User Guide EN V10 www megger com...
Page 28: ...Baker DX Instrument Overview 18 Baker DX 71 030 User Guide EN V10 www megger com...
Page 38: ...Baker DX User Interface Overview 28 Baker DX 71 030 User Guide EN V10 www megger com...
Page 58: ...Setting up the Baker DX Tester 48 Baker DX 71 030 User Guide EN V10 www megger com...
Page 149: ...megger com 139 RIC Templates Figure 141 RIC template 1...
Page 150: ...RIC templates 140 Baker DX 71 030 User Guide EN V10 www megger com Figure 142 RIC template 2...
Page 155: ...Index megger com 145...
Page 156: ...megger com 146...