Procedures for Testing with the Baker ZTX
124 Baker DX 71-030 User Guide EN V10
www.megger.com
6.
The test start screen should look similar to the example shown below.
Figure 137. Armature test with ZTX start screen—Arm Bar mode selected.
Figure 138. Armature test start screen—DX-15A menu—single-coil mode selected.
7.
Select a starting point armature bar to use as a reference. Typically, this will be bar 1, so
the probe or fixture contacts will be placed on bars 1 and 2.
NOTE: When testing coils, a reference will be needed. Refer to the “Determining a Known-good Coil to Use
as a Reference” section found earlier in this chapter for details on this process.
For armature testing, a second operator should be available to start the process and obtain the reference
waveform. When a satisfactory reference is saved and the zero-start override has been set, a single operator
can complete the process.
8.
From this point, the process is essentially the same as the standard process for Surge
testing single coils. Refer to the “Surge testing procedure for single-coil mode” found
earlier in this chapter for detailed instructions.
Summary of Contents for Baker DX
Page 1: ......
Page 2: ......
Page 10: ...Table of Contents viii Baker DX 71 030 User Guide EN V10 www megger com...
Page 28: ...Baker DX Instrument Overview 18 Baker DX 71 030 User Guide EN V10 www megger com...
Page 38: ...Baker DX User Interface Overview 28 Baker DX 71 030 User Guide EN V10 www megger com...
Page 58: ...Setting up the Baker DX Tester 48 Baker DX 71 030 User Guide EN V10 www megger com...
Page 149: ...megger com 139 RIC Templates Figure 141 RIC template 1...
Page 150: ...RIC templates 140 Baker DX 71 030 User Guide EN V10 www megger com Figure 142 RIC template 2...
Page 155: ...Index megger com 145...
Page 156: ...megger com 146...