Procedures for Testing with the DX Host
megger.com
71
3.
If a low MegOhm value is measured, inspect the motor for ground wall insulation
damage or determine if some part of the ground wall insulation has failed. Possible
problems include the following:
Either the slot liner insulation or enamel wire insulation might be burned or
damaged.
The motor might be full of dirt, carbon dust, water, or other contaminants.
Connections to the actual coils might be bad.
The wrong insulation might have been used to connect the coils to the motor’s
junction box.
NOTE: No further testing is worthwhile until you find the reason for low MegOhm readings and make any
necessary corrections.
For more details, refer to
Megger Motor Testing Theory Reference Manual
, which has supporting
information and details about DC testing capabilities and methods.
DC Test Procedure Overview
The general test procedure for DC testing with the DX host includes the following steps:
1.
Ensure low-voltage leads are removed and set aside.
2.
Connect high-voltage test leads.
3.
Select DC tests mode.
4.
Push and hold PTT.
5.
Touch Lock PTT icon.
6.
Touch MOhm/PI icon.
7.
Ramp up test voltage then run test to completion.
8.
Conduct Step Voltage test. Ramp up voltage to next step level then touch Step icon.
9.
Repeat for each step up to second to last step.
10.
Run DC HiPot for last step. Ramp voltage up to proper level then touch HiPot icon.
11.
Alternatively, run just the DC HiPot test or a Ramp test.
12.
Press lock PTT to release.
13.
Save data.
14.
Ensure voltage discharges completely before removing test leads or leave test leads
connected if running Surge test next.
Summary of Contents for Baker DX
Page 1: ......
Page 2: ......
Page 10: ...Table of Contents viii Baker DX 71 030 User Guide EN V10 www megger com...
Page 28: ...Baker DX Instrument Overview 18 Baker DX 71 030 User Guide EN V10 www megger com...
Page 38: ...Baker DX User Interface Overview 28 Baker DX 71 030 User Guide EN V10 www megger com...
Page 58: ...Setting up the Baker DX Tester 48 Baker DX 71 030 User Guide EN V10 www megger com...
Page 149: ...megger com 139 RIC Templates Figure 141 RIC template 1...
Page 150: ...RIC templates 140 Baker DX 71 030 User Guide EN V10 www megger com Figure 142 RIC template 2...
Page 155: ...Index megger com 145...
Page 156: ...megger com 146...