Procedures for Testing with the DX Host
megger.com
63
Resistance Test Procedures
1.
Connect low-voltage resistance test leads as described in chapter 9 “Setting up fixtures,
test accessories, and lead connections.”
CAUTION:
D
ISCONNECT AND LAY ASIDE THE HIGH
-
VOLTAGE TEST LEADS WHEN PERFORMING
RLC
TESTS
.
2.
Select the folder and record to use and check the
Status Bar
to ensure that the
Active
Folder
and
Active Record
display the desired folder and record to be used for the
subsequent RLC tests.
Figure 66. Resistance test start screen.
3.
Touch the
RLC Test Mode
icon.
4.
Ensure that the
Resistance Test Selection
icon is set to resistance test.
5.
If performing temperature compensation, touch the icon for the proper type of
conductor metal: aluminum or copper (
Copper
icon shown above).
NOTE: In the test start screen as shown above, the value that first appears in the
Temp (degC)
field is
originally defined in the system settings. If needed, you can change this value in the next step.
Summary of Contents for Baker DX
Page 1: ......
Page 2: ......
Page 10: ...Table of Contents viii Baker DX 71 030 User Guide EN V10 www megger com...
Page 28: ...Baker DX Instrument Overview 18 Baker DX 71 030 User Guide EN V10 www megger com...
Page 38: ...Baker DX User Interface Overview 28 Baker DX 71 030 User Guide EN V10 www megger com...
Page 58: ...Setting up the Baker DX Tester 48 Baker DX 71 030 User Guide EN V10 www megger com...
Page 149: ...megger com 139 RIC Templates Figure 141 RIC template 1...
Page 150: ...RIC templates 140 Baker DX 71 030 User Guide EN V10 www megger com Figure 142 RIC template 2...
Page 155: ...Index megger com 145...
Page 156: ...megger com 146...