Procedures for Testing with the DX Host
76 Baker DX 71-030 User Guide EN V10
www.megger.com
1.
Touch the
Fast
or
Slow
icons as needed to set the ramp rate.
2.
Use the
Voltage Output Control
knob to set the voltage to the desired DC HiPot
voltage level (2000 volts for this example).
3.
Touch the
DC HiPot
icon to program/set a 60-second test.
4.
Continue with steps 5–7 as described above.
NOTE: The Ramp test is a variation of the HiPot test in which you would ramp to the target test voltage more
slowly to evaluate the linearity of the charging current. Otherwise, the process is the same as conducting a
conventional DC HiPot test.
When ramping the test voltage, be sure to increase the voltage slowly and consistently, and do not stop
ramping until you reach the target test voltage.
Viewing Test Results
1.
View the test results by touching the
Report
,
Display
, and
DC Tests
icons.
2.
Use the submenu icons to find and view results.
Figure 81. Report results submenu icons.
Each of these demonstrated DC tests were chained together in a recommended best-practice
approach, but you may separate and perform them individually or in other combinations as
required or preferred.
Figure 82. DC Tests results screen.
Summary of Contents for Baker DX
Page 1: ......
Page 2: ......
Page 10: ...Table of Contents viii Baker DX 71 030 User Guide EN V10 www megger com...
Page 28: ...Baker DX Instrument Overview 18 Baker DX 71 030 User Guide EN V10 www megger com...
Page 38: ...Baker DX User Interface Overview 28 Baker DX 71 030 User Guide EN V10 www megger com...
Page 58: ...Setting up the Baker DX Tester 48 Baker DX 71 030 User Guide EN V10 www megger com...
Page 149: ...megger com 139 RIC Templates Figure 141 RIC template 1...
Page 150: ...RIC templates 140 Baker DX 71 030 User Guide EN V10 www megger com Figure 142 RIC template 2...
Page 155: ...Index megger com 145...
Page 156: ...megger com 146...