IMPULSE•G+/VG+ Series 4 Technical Manual
November 2022
Page 51
4.2.1 Keypad LED and Button Functions
Some of the keypad buttons, whose functions are described below, are dual-purpose. The dual-purpose keys have
one function when used in a view-only mode, and another function when used in a programming mode.
*1 The STOP key has highest priority. Pressing the STOP key will always cause the VFD to stop the motor, even if a Run command is active at
any external Run command source.
*2 The LO/RE key can only switch between LOCAL and REMOTE when the VFD is stopped. To enable the LO/RE key to switch between
LOCAL and REMOTE, set parameter O02-01 = 1.
1
The functions assigned to F1 and F2 vary depending on the current
displayed menu. The name of each function appears in the lower half of the
display window.
2
•
Returns to the previous display
•
Moves the cursor one space to the left.
•
Pressing and holding this button will return to the home screen.
3
•
Moves the cursor to the right.
•
Resets the VFD to clear a fault.
4
Starts the VFD when in LOCAL mode.
5
Scrolls up to display the next item, selects parameter numbers, and
increments setting values.
6
Scrolls down to display the previous item, selects parameter numbers, and
decrements setting values.
7
Stops VFD operation.
*1
8
•
Enters parameter values and settings.
•
Selects a menu item to move between displays.
9
•
Displays the phone number for the Magnetek Service department.
•
Switches VFD control between the keypad (LOCAL) and an external
source (REMOTE) for the Run command and frequency reference.
*2
•
Pressing the key three times resets the maintenance timer, U01-52.
10
Lit while the VFD is operating the motor.
Flashing when the VFD has a phantom fault.
11
Lit while the keypad is selected to run the VFD (LOCAL mode).
12
Off during normal operation (no fault or alarm).
Illuminated when the VFD detects an alarm or error.
Flashes when an alarm occurs, when an oPE is detected, or when an error
occurs during Auto-Tuning.